Thermo Products CDX1-125N, CDX1-75N, CHX1-125N, CHX1-75N StageBlower Settings from factory Table

Models: CDX1-100N CDX1-125N CHX1-100N CHX1-75N CHX1-125N CDX1-75N

1 59
Download 59 pages 47.89 Kb
Page 34
Image 34

All installations and services must be performed by qualified service personnel.

Modifications to ECM blower speed settings are done using the S3 and S4 dip switch controls. (Labeled 1 to 8 in Figure 21). Thermo Pride two-stage furnaces are factory shipped at the CFM settings listed below in Table 4.

2-Stage Blower Settings (from factory)

Table 4

 

Control Board

Heating

Heating

Constant Fan

Cooling

Unit

Dip Switch

CFM

CFM

CFM

CFM

 

Settings

(low fire)

(high fire)

 

 

 

CDX1-75

1-7 Off

885

1012

500

1000

8 On

 

 

 

 

 

 

 

 

 

 

 

CHX1-75

1-8 Off

760

931

500

1000

 

 

 

 

 

 

CDX1-100

1-7 Off

1094

1340

600

1200

8 On

 

 

 

 

 

 

 

 

 

 

 

CHX1-100

1-8 Off

1015

1243

600

1200

 

 

 

 

 

 

CDX1-125

1-7 Off

1366

1673

700

1400

8 On

 

 

 

 

 

 

 

 

 

 

 

CHX1-125

1-8 Off

1270

1556

700

1400

 

 

 

 

 

 

For adjustments to the Cooling CFM settings, as well as all additional CFM changes, please reference the dip switch tables listed in the ECM operation manual. (Included with every furnace.)

5. FIELD WIRING AND REPLACING WIRING

Field wiring between the furnace and devices not attached to the furnace shall conform with the temperature limitation for Type T wire[63°F rise (35°C)] when installed in accordance with the manufacturer’s instructions. If any of the original factory supplied furnace wiring is replaced or a separate device other than the thermostat is wired internal to the unit 105°C thermoplastic or equivalent wire must be used.