Thermo Products omd-70 service manual closed? If 120 VAC is

Models: omd-70

1 49
Download 49 pages 20.13 Kb
Page 38
Image 38
closed? If 120 VAC is

All installations and services must be performed by qualified service personnel.

After pre-purge, does the ignition control (GMD) or the oil primary (OMD) produce a spark at the ignition electrodes?

Yes

 

 

 

On the GMD,has the burner

 

 

 

motor centrifugal switch

 

 

 

closed? If 120 VAC is

No

Is there 24 VAC across the power

No

measured across the switch,

replace the burner motor. Else,

terminals of the ignition control

 

 

 

replace thermostat. On the OMD,

 

module (GMD) or 120 VAC across

 

 

 

try resetting the oil primary

 

the ignition transformer (OMD)?

 

 

 

control by depressing the

 

 

 

 

 

 

RESET button. Check cad cell

 

 

 

function. If all else fails,

 

Yes

 

replace the oil primary.

 

 

 

 

Check wiring to the electrodes and

 

 

 

ignition control module fuse (GMD)

 

 

 

or the ignition transformer and the

 

 

 

electrodes (OMD). Also, check ignition

 

 

electrode gap. Reset if necessary.

 

 

 

Replace electrodes, ignition control

 

 

 

module (GMD) or ignition transformer (OMD).

 

While ignition electrodes are sparking does fuel valve open?

Yes

No

Is there 24 VAC (GMD) across

"MV" terminals on ignition

control module during ignition attempt. Does the oil solenoid valve have 120 VAC across it during the ignition attempt (OMD)?

Yes

Check wiring to fuel valve.

If valve does not open,

replace fuel valve.

No

On the GMD, reset the module by interrupting power to system for more than one second. If this does not work, replace ignition control module. On the OMD, try resetting the oil primary control by depressing the RESET button. If this does not work, replace the oil primary.

37

Page 38
Image 38
Thermo Products omd-70 service manual closed? If 120 VAC is