All installations and services must be performed by qualified service personnel.
After
Yes
|
|
| On the GMD,has the burner | |
|
|
| motor centrifugal switch | |
|
|
| closed? If 120 VAC is | |
No | Is there 24 VAC across the power | No | measured across the switch, | |
replace the burner motor. Else, | ||||
terminals of the ignition control |
| |||
|
| replace thermostat. On the OMD, | ||
| module (GMD) or 120 VAC across |
| ||
|
| try resetting the oil primary | ||
| the ignition transformer (OMD)? |
| ||
|
| control by depressing the | ||
|
|
| ||
|
|
| RESET button. Check cad cell | |
|
|
| function. If all else fails, | |
| Yes |
| replace the oil primary. | |
|
|
| ||
| Check wiring to the electrodes and |
|
| |
| ignition control module fuse (GMD) |
|
| |
| or the ignition transformer and the |
|
| |
| electrodes (OMD). Also, check ignition |
| ||
| electrode gap. Reset if necessary. |
|
| |
| Replace electrodes, ignition control |
|
| |
| module (GMD) or ignition transformer (OMD). |
|
While ignition electrodes are sparking does fuel valve open?
Yes
No
Is there 24 VAC (GMD) across
"MV" terminals on ignition
control module during ignition attempt. Does the oil solenoid valve have 120 VAC across it during the ignition attempt (OMD)?
Yes
Check wiring to fuel valve.
If valve does not open,
replace fuel valve.
No
On the GMD, reset the module by interrupting power to system for more than one second. If this does not work, replace ignition control module. On the OMD, try resetting the oil primary control by depressing the RESET button. If this does not work, replace the oil primary.