Check all wiring for

All installations and services must be performed by qualified service personnel.

Yes

 

 

 

No

 

 

 

No

 

 

Does system run until

 

Has the high limit thermostat

 

Check all wiring for

 

 

or auxiliary high limit

 

 

 

thermostat is satisfied?

 

 

 

 

 

loose connections.

 

 

thermostat activated?

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

Check for reduced airflow through

 

 

 

the furnace. This may be caused

 

 

 

by an excessively restrictive duct

 

Yes

 

system, an inadequate amount of

 

 

 

supply air,especially for furnaces

 

 

 

installed in closets, or extremely

 

 

 

dirty air filters. Also, check and

 

 

 

confirm heat input rate to unit is

 

 

 

within specifications.

 

Does burner shut off

No

Check for short in wire

 

when thermostat is

 

to thermostat. Replace

 

satisfied?

 

thermostat, if necessary.

 

Yes

 

 

 

 

 

Check fan timer settings

 

Does the circulating air

No

against those on connection

Yes

blower turn off after

diagram. Is fan selector

 

Replace fan timer.

thermostat is satisfied

 

switch set on "manual".

 

 

within 4 minutes?

 

Reset if necessary. Does

 

 

 

fan still fail to turn off?

 

Yes

 

 

 

Troubleshooting Complete.

 

 

 

 

 