All installations and services must be performed by qualified service personnel.

M. FLUE GAS COMBUSTION ANALYSIS

: Burner adjustments must be confirmed by instrumentation. Failure to use accurate or calibrated instrumentation to correctly setup the burner may result in reduced efficiency, sooting, and/or the production of hazardous carbon monoxide gas.

For typical burner combustion analysis results, refer to the table below.

BURNER COMBUSTION PARAMETERS

FURNACE MODEL OME-72

LOW-FIRE

HIGH-FIRE

 

FUEL TYPE

#1 OR #2 FUEL OIL

#1 OR #2 FUEL OIL

CO (CARBON MONOXIDE)

50PPM OR LESS

50PPM OR LESS

CO2 (CARBON DIOXIDE)

10.5-11%

11-12%

 

O2 (OXYGEN)

4.5-6%

4.5-6%

 

SMOKE SPOT RATING

0

0

 

AIR SHUTTER ADJUSTMENT

OPEN TO POSITION 3.5

OPEN TO POSITION 3.5

32

Page 34
Image 34
Thermo Products ome-72d36 service manual Flue GAS Combustion Analysis, Burner Combustion Parameters