All installations and services must be performed by qualified service personnel.

Yes

 

 

 

No

 

Are the thermostat wires

Correct wire connections.

 

 

connected properly?

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Is there combustion airflow to the furnace?

Yes

Is the oil primary control

Yes

 

 

supplying 24 VAC to the

 

 

 

 

thermostat?

 

 

 

 

No

Try resetting the oil primary control. Replace the oil primary control, if necessary.

No

Is there 120 VAC across

No

 

 

 

the burner motor?

 

 

 

 

Yes

Is the blower impeller spinning? If so, check for blockages in or a collapsed air duct. Is the air boot shutter open adequately.

Yes

Replace thermostat.

Is the oil primary control receiving power? Reset primary control. If resetting the primary does not work, replace control.

Check wiring to burner motor. If okay, replace burner motor.

35