Thermo Products PHCFA072DV4R a. Combustible material, b.Non-combustiblematerial, Type Of, From

Models: PHCFA072DV4R

1 55
Download 55 pages 42.07 Kb
Page 7
Image 7
a. Combustible material:

a. Combustible material:

“...materials made of or surfaced with wood, compressed paper, plant fibers, or other materials that are capable of being ignited and burned. Such materials shall be considered combustible even though flame proofed, fire-retardant treated, or plastered.”

b.Non-combustible material:

“...material that is not capable of being ignited and burned; such as material consisting entirely of, or a combination of, steel, iron, brick, concrete, slate, asbestos, glass, and plaster.”

b.Non-combustible material:TYPE OFFROMTOP &FROM THEMODEL NO.SIDES OFFRONTREARUNITFLUE/VENTFURNACEPLENUMHighboyOHCFA072DV4R: Carefully read and thoroughly understand the following guidelines and warnings before continuing with the installation of this appliance. Failure to follow these guidelines can cause improper and unsafe operation of this appliance. Unsafe operation can result in substantial property damage, severe personal injury, or death.

1.This appliance shall be used with only the type of fuel oil for which it is approved. Refer to the appliance-rating label for the required type of fuel.

2.This appliance is an oil-fired furnace designed for installation on non-combustible materials.

3.Ensure that adequate combustion and ventilation air is available to the unit.

4.The airflow resistance of the duct system attached to this appliance must fall within the allowable external static pressure range for this unit. Refer to the Airflow Requirements and Sizing of Ductwork section of this manual.

5.Make sure supply and return air ducts are completely sealed to the appliance casing. Refer to the Airflow Requirements and Sizing of Ductwork section of this manual.

Table 1: MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

TYPE OF

 

FROM

 

 

TOP &

FROM THE

 

MODEL NO.

SIDES OF

 

FRONT

SIDES OF

REAR

UNIT

 

FLUE/VENT

 

FURNACE

 

 

PLENUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Highboy

OHCFA072DV4R

0”

 

Note 1

1”

0”

0”

 

 

 

 

 

 

 

 

 

Note: 1 OHC front clearance

6” for Closet, 24” for Alcove.

 

The minimum clearances listed in the preceding table are for fire protection. Clearance for servicing the front of the furnace should be at least 24 inches.

NOTE: The OHC furnace is approved for closet installation.