TOA Electronics 600 Vertical Vent Figures/Tables, Table B, H Maximum, Top Vent - STRAIGHT

Models: 600

1 28
Download 28 pages 9.94 Kb
Page 13
Image 13
VERTICAL VENT FIGURES/TABLES

VERTICAL VENT FIGURES/TABLES

Note: Secure Vent (rigid vent pipe) is shown in the figures; Secure Flex (flexible vent pipe) may also be used.

WARNING: UNDER NO CIRCUM - STANCES MAY SEPARATE SECTIONS OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.

Note: It is very important that the horizontal/ inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of ¹⁄₄" rise per foot (20 mm per meter) which is ideal, though rise per foot run

TABLE A

V MINIMUM

H Maximum

 

 

 

 

feet

(m)

feet

(m)

 

 

 

 

1

(0.305)

2

(0.61)

 

 

 

 

2

(0.61)

4

(1.222)

 

 

 

 

3

(0.914)

6

(1.86)

 

 

 

 

4

(1.22)

8

(2.4)

 

 

 

 

V + H = 40 feet (12.4 m) Max.

H = 8 feet (2.4 m) Max.

*Ceiling

Firestop/Spacer

(SV4.5BF)

*When using Secure Flex, use Firestop/Spacer SF4.5BF

**When using Secure Flex, use Firestop/Spacer SF4.5HF

ratios that are smaller are acceptable all the way down to at or near level.

Note: SV4.5BF (Secure Vent), SF4.5BF (Se- cure Flex) firestop/spacer must be used any- time vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)firestop/spacer must be used anytime vent pipe passes through a com- bustible wall.

Note: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.

40 feet (12.2 meters)

*Ceiling H Maximum Maximum Firestop/Spacer

(SV4.5BF)

*When using Secure Flex, use Firestop/Spacer SF4.5BF

Figure 27 - Top Vent - STRAIGHT

**Wall

Firestop/Spacer

(SV4.5HF)

V

H

Figure 28 - Rear Vent - ONE 90 DEGREE ELBOW

 

H

 

TABLE B

 

 

V MINIMUM

H Maximum

 

 

 

 

feet

(meters)

feet

(meters)

 

*Ceiling

1

(0.305)

5

(1.52)

 

Firestop/Spacer

2

(0.610)

10

(3.1)

 

(SV4.5BF)

 

 

3

(0.914)

15

(4.65)

 

*When using Secure Flex,

4

(1.22)

20

(6.2)

 

V + V1+ H = 40 feet (12.4 m) Max.

V1

use Firestop/Spacer

 

SF4.5BF

 

H = 20 feet (6.2 m) Max.

 

 

 

 

V

 

 

 

 

 

**Wall

 

 

 

 

 

Firestop/Spacer

 

 

 

 

 

(SV4.5HF)

 

 

 

 

 

*Ceiling

 

 

 

 

 

Firestop/Spacer

 

 

 

 

 

(SV4.5BF)

 

 

 

 

**When using Secure

 

 

 

 

Flex, use Firestop/Spacer

 

 

 

 

 

SF4.5HF

 

 

 

 

Figure 29 - Top Vent - TWO 90 DEGREE ELBOWS

 

 

 

 

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

13

Page 13