HORIZONTAL VENT FIGURES/TABLES
(continued)
| H1 | H |
|
| TABLE H |
|
| |
|
| V Minimum | H Maximum | H+H1 Maximum | ||||
|
|
| ||||||
|
|
| feet | (m) | feet | (m) | feet | (m) |
|
| *Wall | 1 | (0.305) | 2 | (0.610) | 5 | (1.52) |
|
|
|
|
|
|
|
| |
|
| Firestop/Spacer | 2 | (0.610) | 4 | (1.22) | 10 | (3.1) |
|
| (SV4.5HF) | 3 | (0.914) | 6 | (1.86) | 15 | (4.65) |
|
|
| ||||||
|
| **Ceiling | 4 | (1.22) | 8 | (2.48) | 20 | (6.2) |
|
| Firestop/Spacer | ||||||
|
|
| V+H+H1 = 40 feet (12.4 m) Max. | |||||
|
| (SV4.5BF) |
| |||||
*When using |
|
|
| H = 8 feet (2.48 m) Max. |
| |||
Secure Flex, use |
| *Wall |
| H + H1 = 20 feet (6.2 m) Max. |
| |||
Firestop/Spacer |
| Firestop/Spacer |
|
|
|
|
|
|
SF4.5HF | V | (SV4.5HF) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
**When using |
|
|
|
|
|
|
|
|
Secure Flex, use |
|
|
|
|
|
|
|
|
Firestop/Spacer |
|
|
|
|
|
|
|
|
SF4.5BF |
|
|
|
|
|
|
|
|
Square termination (SV4.5HTS) shown. Round Termination (SV4.5HTR) may only be used on
See Table 3 on page 17 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 40 - Rear Vent - TWO 90 DEGREE ELBOWS
| *Wall Firestop/Spacer | |
| (SV4.5HF) | |
| H | |
H1 | V | |
| ||
*When using Secure Flex, | *Wall Firestop/Spacer | |
use Firestop/Spacer | ||
(SV4.5HF) | ||
SF4.5HF | ||
**Note - When using |
| |
Secure Flex, use | **Ceiling | |
Firestop/Spacer SF4.5BF | Firestop/Spacer | |
| (SV4.5BF) |
TABLE J
V MINIMUM | H + H1 Maximum | ||
feet | (m) | feet | (m) |
|
|
|
|
1 | (0.305) | 5 | (1.52) |
2 | (0.610) | 10 | (3.1) |
3 | (0.914) | 15 | (4.65) |
4 | (1.22) | 20 | (6.2) |
|
|
|
|
V + H+ H1 = 40 feet (12.4 m) Max. H + H1= 20 feet (6.2 m) Max.
18
Square termination (SV4.5HTS) shown. Round Termination (SV4.5HTR) may also be used.
The Small Square Termination (SV4.5HTSS) may only be used on
See Table 3 on page 17 as an aid in venting component selection for a particular range of exterior wall thicknesses.
Figure 41 - Top Vent - TWO 90 DEGREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.