Toshiba 1000 Dry Contact Interface optional card, DB9 Male Connector Outline facing connector

Models: 1000

1 54
Download 54 pages 29.07 Kb
Page 38
Image 38
5.2Dry Contact Interface (optional card)

5.2Dry Contact Interface (optional card)

DB9 Male Connector Outline

(facing connector)

Pin #

 

Description
I/O Type

1

UPS fail, relay contact, normally open, active close.

output

2

Summary alarm, relay contact, normally open, active close.

output

 

One of the following signals activate this signal:

 

 

1)

Output fault

 

 

2)

Bus fault

 

 

3)

Over temperature

 

 

4)

Overload

 

 

5)

Over Charging

 

 

6)

Battery test fail

 

 

7)

Charger failure

 

3

GND for secondary

 

4

Remote shutdown

input

5

Common

 

6

Bypass active, normally open, active close

output

7

Battery low, normally open, active close

output

8

Battery mode shutdown

input

9

Utility fail, normally open, active close

output

Table 2 : DryContact Pin Out Signal Chart

5.3USB Port

Connecting the UPS to a computer using the USB port of the computer requires USB compliant hardware, PC operating system support, and a UPS driver. The RS232 serial

15

Page 38
Image 38
Toshiba 1000 Dry Contact Interface optional card, DB9 Male Connector Outline facing connector, USB Port, Pin #, I/O Type