3. Storage
4. External Battery
5. Idle Batteries
1. Temperature

LIMITATIONS AND EXCLUSIONS

1.This limited warranty shall not cover the UPS, UPS parts, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):

Valve Regulated Lead Acid (VRLA) Batteries for Toshiba UPS Required Operating, Installation, and

Maintenance Conditions

Annual Average Temperature is to be 77°F (25°C) with no greater temperature of 89°F (32°C) for more than 30 days

 

 

Maximum Number of Cycles (24 Months)***

 

Discharge Time

Battery > 9AHr

Battery < 9AHr

2. Maximum # of Full

30 min

20

69

15 min

25

86

Charge/Discharge

10 min

32

110

Cycles

5 min

38

130

 

***> 9AHr Typically extended runtimes < 9AHr Typically Single Phase Systems.

While UPS is in Transit or in storage, it must always be in a suitable temperature (as stated above)

Parallel battery string applications must be approved by TIC in writing

User must recharge the batteries if not in use (charged) for more than 6 months

Credit for Replacement Battery When Approved Warranty

Time from Shipments

UPS Batteries

Cost to Customer

Months

% Credit

% List Price

0-24

100

0

25-30

55

45

31-36

45

55

37-42

35

65

43-48

25

75

49-54

15

85

55-60

5

95

27

Page 50
Image 50
Toshiba 1000 manual Limitations and Exclusions