4.4Front Panel Settings

4.4Front Panel Settings

Listed below are the default settings of the primary UPS parameters.

Settings

Options

Default

Remarks

1) O/P VOLT SET

100V/110V/115V/120V/127V

120V

120V (FOR LV series)

(output voltage

208/220/230/240 Vac

230V

230V (FOR HV series)

set)

 

 

 

 

 

 

 

2) I/P FREQ SET

+/- 2%

+/- 5%

Input Frequency range in

(input frequency

+/- 5%

 

Free Run mode

setting)

+/- 7%

 

 

3) I/P BYPASS

+/- 10%

+10%

Input Voltage range when

SET

+10% -15%

-15%

Bypass mode is on

(input bypass

+15% -20%

 

 

setting)

 

 

 

4) FREE RUN

ON/OFF

ON

If ON, enable UPS runs on

SET

 

 

Asynchronous mode.

 

 

 

For example:

 

 

 

If input freq 55Hz

 

 

 

output freq stays at 60Hz.

 

 

 

If OFF, disable UPS runs on

 

 

 

synchronous mode.

 

 

 

For example:

 

 

 

If input freq 55Hz,

 

 

 

UPS will go to battery mode.

5) HE MODE SET

ON/OFF

OFF

If ON, enable UPS runs in

 

 

 

High efficiency mode. The

 

 

 

unit will be in bypass mode

 

 

 

with 95% or higher

 

 

 

efficiency.

 

 

 

If OFF, the unit will be in the

 

 

 

online mode with 85%

 

 

 

efficiency.

6) MANUAL

ON/OFF

OFF

If ON, enable UPS switch to

BYPASS

 

 

Bypass mode immediately.

 

 

 

 

12

Page 35
Image 35
Toshiba 1000 manual Front Panel Settings, Listed below are the default settings of the primary UPS parameters