Toshiba manual Power Range 1000-3000 VA, RemotEye II and EMD

Models: 1000

1 54
Download 54 pages 29.07 Kb
Page 48
Image 48
8.2Power Range 1000-3000 VA (230V)

8.2Power Range 1000-3000 VA (230V)

Tower

International

UT1E1E010C6

UT1E1E015C6

 

UT1E1E020C6

UT1E1E030C6

 

230V Model

 

 

 

 

 

Rack-

International

UT1E1E010C6R

UT1E1E015C6R

 

UT1E1E020C6R

UT1E1E030C6R

mount

230V Model

KB2

KB2

 

KB2

KB2

(2U)

 

 

 

 

 

 

Input

Voltage

 

230 VAC (161 – 276 V)

 

 

(International)

 

 

 

 

 

 

Voltage Range

 

+20% to -30%

 

 

(International)

 

 

 

 

 

 

Capacity (VA)

1000 VA

1500 VA

 

2000 VA

3000 VA

 

Capacity (W)

700 W

1050 W

 

1400 W

2100 W

 

Frequency

 

50 / 60 Hz

auto sensing

 

 

Power Factor

 

Greater than 0.97

 

 

Topology

True on-line, Double conversion Input PF correction

Output

Voltage

 

230 VAC

 

 

(International)

 

 

 

 

 

 

Frequency

 

50 / 60 Hz auto sensing

 

 

Wave Form

 

Sine wave, zero transfer time

 

 

Load Power

 

 

0.70

 

 

Factor

 

 

 

 

 

 

Efficiency

 

Greater than 86%

 

 

AC/DC/AC

 

 

 

 

 

 

Rated Current

4.3 A

6.5 A

 

8.7 A

13 A

 

(International)

 

 

 

 

 

 

Overload

 

125% for 1 min.,

150% for 10 sec.

 

 

Capacity

 

 

 

 

 

 

Crest Factor

 

3.0 at full load

 

Battery

DC Voltage

36 V / 12 V 9 AH x 3

 

72V / 12 V

72V / 12 V 9AH x

 

(Tower & 2U)

 

 

 

7.2AH x 6

6

 

Backup Time

7 min

6 min

 

7 min

6 min

 

(Tower & 2U)

(full load)

(full load)

 

(full load)

(full load)

 

Interface

RS-232

and USB standard

RemotEye II® and EMD

option

Physical

Dimensions

16.5”L x 6.0”W x 9.4”H

 

16.7" L x 8.9" W x 14.2" H

 

(Tower)

 

 

 

 

 

 

Dimensions

16.7”L x 16.9”W x 3.5”H

 

"25.0""L x 16.9""W x 3.5""H"

 

(2U)

 

 

 

 

 

 

Weight

35.6 lbs /

37.4 lbs /

 

68.4 lbs /

72.6 lbs / 71.5 lbs

 

(Tower/2U)

37.6 lbs

37.6 lbs

 

69.5 lbs

 

 

Line Cord

 

IEC

320

 

 

(International)

 

 

 

 

 

 

Receptacles

IEC 320 (4 / 4)

 

IEC 320 (8 / 8)

 

(Tower/2U)

 

 

 

 

 

 

International

 

 

 

 

 

Environ-

Operating

 

0 - 40°C (32 - 104°F)

 

ment

Temperature

 

 

 

 

 

 

Altitude

 

11500 ft (3500 m) above sea level

 

Warranty

 

Three years on electronics

 

 

 

 

 

Two years full replacement on battery (See Toshiba warranty policy for full details.)

 

 

 

 

 

 

 

Standards - Safety: EN50091-1-1, Emissions: EN50091-2, Immunity: EN50091-2 B (1000-1500VA)