79

G8000 Series Installation and Operation Manual

Appendix A - Installation Planning Guides

TOSHIBA G8000 Series UPS
Installation Planning Guide for 80kVA UPS

Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx)

Rev. 2.2Page 1of 3G8000-IPG-80kVA
General Mechanical Information
Dimensions
(W x D x H)
Weight Floor
Loading
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Inches
Lbs.
Lbs./ft. 2
Btu/Hr
Top
Front
Bottom
Sides
36.8” x 32.5” x 79.2
1,740
210
28,321
15.75”
43.5”
0”
0”
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
External Feeder Wire Size: Min. Max. Per Phase
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating
89(100)
>0.99
107 (120)
150 A
1/0 (2) x 2/0
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max.Per Phase // Min. Max. for Neutral
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating
80
1.0
96
125 AT
1/0 (2) x 2/0 // (2) x 1/0 (2) x 2/0
DC Backup Input (Battery -360VDC Nom./Flywheel 550VDC Nom.)
Backup System
DC Capacity for Full
Load Output
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection*
External Feeder Wire Size:
Min. Max.
kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating
Battery
88
292
300 A
(2) x 1/0 (2) x 3/0
Flywheel
88
158
175 A
2/0
*If required. Most Battery and Flywheel Cabinets are equipped with built-in breakers.
AC Output (480/277V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase // Min. Max. for Neutral
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating
80
1.0
96
125 A
1/0 (2) x 2/0 // (2) x 1/0 (2) x 2/0
Important Notes:
1. CABLE ACCESS Bottom only.
2. Maximum Current required at Primary AC Input based on full
load output and maximum battery charging current.
3. Output load conductors are to be installed in separate
conduit from input conductors.
4. Control wires and power wires are to be installed in separate
conduits.
5. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
6. Wiring shall comply with all applicable national and local
electrical codes.
7. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
-Primary AC Input: 3φ, 3-wire + ground.
-Alternate AC Input: 3φ, 4-wire + ground.
-AC Output: 3φ, 4-wire + ground.
-DC Input: 2-wire (Positive/Negative) + ground.
8. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
9. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67VPC.
10. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
11. Weights do not include batteries or other auxiliary equipment
external to the UPS.
12. Cable sizing calculations based on the following assumptions:
-Minimum size is smallest size based on ampacity at 30 °C.
-Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
-Neutral sized for 2X phase current.
-Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
-Temperature rating of copper conductors/terminals: 75 °C.
-Reference: 2005 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
13. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
TOSHIBA INTERNATIONALCORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (877) 867-8773
Fax: (713) 896-5212
Web Site: www.toshiba.com/ind

80kVA IPG