Toshiba DEV002Z instruction manual 5.3. f830 Assembly Object Setting

Models: DEV002Z

1 20
Download 20 pages 45.89 Kb
Page 16
Image 16
5.3. f830: Assembly Object Setting

E6581295

5.3. f830: Assembly Object Setting

The Input/Output Instance of DEV002Z is set up by this parameter.

The DEV002Z supports both the standard DeviceNet AC Drive profile Instances 20/70, 21/71 and user defined Instances 100/150, 101/151, 102/152.

*For an explanation of f830 = 0 (Instance 20/70), 1 (Instance 21/71), 3 (Instance 101/151) and 4 (Instance 102/152), refer to the function manual (E6581281).

f830=2 (Instance 100/150)

Byte

bit7

bit6

bit5

bit4

bit3

bit2

bit1

bit0

0

DC

Acc./Dec.

PI control

Motor

Preset

Preset

Preset

Preset

braking

#1/#2

#1/#2

Speed 4

Speed 3

Speed 2

Speed 1

 

 

 

 

 

 

 

 

 

 

 

1

Command

Frequency

Reset

Emerg.

Free run

Run/Stop

Forward/

Jog

link

link

trip

stop

(ST)

Reverse

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Drive Reference Speed Hz (Low byte)

 

 

3

 

 

Drive Reference Speed Hz (High byte)

 

 

 

 

 

 

 

 

 

 

 

 

Output Instance 100 format

 

 

 

Byte

bit7

bit6

bit5

bit4

bit3

bit2

bit1

bit0

0

DC

Acc./Dec.

PI control

Motor

(Reserved)

ALARM

Fault

Fault FL

braking

#1/#2

#1/#2

(fc91)

 

 

 

 

 

 

 

 

 

 

 

READY

READY

Emerg.

Free run

 

Forward/

 

1

(Reserved)

without

with

Run/Stop

Jog

stop

(ST)

Reverse

 

 

ST/RUN

ST/ RUN

 

 

 

 

 

 

 

 

 

2

 

 

Drive Actual Speed Hz (Low byte)

 

 

3

 

 

Drive Actual Speed Hz (High byte)

 

 

 

 

 

 

 

 

 

 

 

 

Input Instance 150 format

 

 

 

*Drive Reference Speed command value

A frequency should be specified in hexadecimal notation in units of 0.01Hz.

For example, to set the frequency at 60Hz, since the minimum unit of frequency is 0.01Hz, you have to enter the following number.

60÷0.01 = 6000 = 0x1770 (hexadecimal)

- 15 -