Trane 750 CFM manual Trouble Shooting Checklist, Hazardous Service Procedures, Problem, Correction

Models: 750 CFM 1500 CFM

1 40
Download 40 pages 23.79 Kb
Page 31
Image 31
Trouble Shooting

Trouble Shooting

Checklist

!WARNING

Hazardous Service Procedures!

The maintenance and trouble shooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings pro- vided throughout this manual concerning these procedures. When possible, disconnect all electrical power including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components per these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious in- jury.

If operating difficulties are encountered, refer to page 31 and 32 for probable causes and corrective measures. If suggested corrective measures have been taken, and the trouble still persists, contact the control supplier or the local Trane Sales Of- fice.

Problem

Heating Cooling Cause

Correction

Room too warm

(outside air temperature is below 35° F)

X

Main power off

Check fuses

 

 

 

X

Room sensor is not properly set

Reset room sensor temperature

 

 

 

 

Room sensor is providing a false reading due

Start the warm-up cycle earlier in the

X

to walls being cold from the night temperature

morning to provide appropriate time-

 

setting.

frame to increase room temperature prior

 

to space occupation.

 

 

 

 

 

 

Sensor is mounted on a block wall that is

 

X

leaking cold air into the room through the

Relocate sensor.

 

mounting holes.

 

 

 

Replace malfunctioning component, or

X

Face and bypass damper, or coil valve is

contact the control’s contractor, or if Trane

malfunctioning.

controls, see CNT-SVX04A-EN for more

 

 

 

information concerning Tracer™ controls.

 

X

Room sensor is not properly set

Reset room sensor temperature

 

 

 

 

 

 

 

Replace malfunctioning component, or

 

X

Face and bypass damper or coil control valve

contact the control’s contractor, or if Trane

 

controls, see CNT-SVX04A-EN for more

Room too warm

 

is malfunctioning.

information concerning Tracer™ controls.

(outside air temperature is above 35° F)

 

 

 

 

 

 

 

 

X

OA damper is in the closed position

Ensure OA damper is in the open

 

position.

 

 

 

 

 

 

 

 

X

Clogged filter

Replace filter

 

 

 

 

 

X

Control valve is malfunctioning

Check flow of hot water through the

 

control valve.

 

 

 

 

 

 

Check the boiler reset schedule to

 

X

Boiler

determine if the loop temperature can be

 

 

 

decreased.

Room too warm

X

Steam

Check the operation of the control valves

(outside air temperature is above 35° F)

 

 

 

 

 

The economics of the unit ventilator

Unit utilizes Wall Fin auxiliary radiation:

 

 

 

 

 

selection dictate that, in most cases, the

 

 

 

unit will be sized to provide adequate

 

X

Outside air temperature is above 60 to 65° F

natural (ventilation) cooling without

 

 

 

outside temperatures up to 60-65 F.

 

 

 

Above this point, a changeover should be

 

 

 

made to the mechanical cooling cycle.

 

 

 

 

UV-SVN03D-EN

31

Page 31
Image 31
Trane 750 CFM manual Trouble Shooting Checklist, Hazardous Service Procedures, Problem, Heating Cooling Cause, Correction