Trane 1500 CFM Trouble Shooting Checklist, Problem Room too cool, Heating Cooling, Cause, Motor

Models: 750 CFM 1500 CFM

1 40
Download 40 pages 23.79 Kb
Page 32
Image 32
Problem

Trouble Shooting Checklist

Problem

Room too cool

Heating Cooling

Cause

Correction

X

Room sensor is not properly set

Reset room sensor temperature

 

 

 

X

Clogged filter

Replace filter

 

 

 

 

 

Replace malfunctioning component, or

X

Face and bypass damper, or coil valve is

contact the control’s contractor, or if Trane

malfunctioning.

controls, see CNT-SVX04A-EN for more

 

 

 

information concerning Tracer™ controls.

 

 

 

X

OA damper is in the open position

Ensure OA damper is in the closed or

minimum outside air position.

 

 

 

Boiler pressure or temperature design

On hot water and steam type units, check

X

the boiler pressure or temperature to

requirements not being met

ensure that the requirements are being

 

 

 

met.

Room too cool

X

Radiation controls malfunctioning

Check the operation of the wall fin

Unit utilizes Wall Fin auxiliary radiation:

controls.

 

 

 

X

Room sensor is not properly set

Reset room sensor temperature

 

 

 

 

 

X

Clogged filter

Replace filter

 

 

 

 

 

 

 

Replace malfunctioning component, or

 

X

Face and bypass damper, or coil valve is

contact the control’s contractor, or if Trane

 

malfunctioning.

controls, see CNT-SVX04A-EN for more

Room too hot

 

 

 

information concerning Tracer™ controls.

 

 

 

 

 

X

OA damper is in the open position

Ensure OA damper is in the minimum

 

outside air position.

 

 

 

 

X

Chiller temperature design requirements not

Check the temperature of the water

 

leaving the chiller to ensure that it meets

 

being met

 

 

design requirements.

 

 

 

 

 

 

 

 

X

If the motor fails to start, and other motors on

Check the unit switch to ensure it is in the

Motor

the same circuit are functioning

ON position.

 

 

 

 

 

X

If the motor fails to start, and other motors on

Check for loose switch or motor

 

the same circuit are functioning

connection.

 

 

 

 

 

 

32

UV-SVN03D-EN

Page 32
Image 32
Trane 1500 CFM Trouble Shooting Checklist, Problem Room too cool, Heating Cooling, Cause, Correction, Room too hot, Motor