Installation

Figure 2- Rigging the unit - RTUB 207-208

Figure 3- Rigging the unit - RTUB 210-224

Figure 4- Rigging the unit - RTCA 108-216

 

Table 3 - Sling Lengths (mm) for lifting

 

 

 

 

 

 

 

 

A

B

C

D

E

 

RTUB unit size

 

 

 

 

 

 

 

207-208

2200

3000

2600

2100

-

 

 

210-211-212

2400

3000

2550

3150

3650

 

 

214-216-217

2500

3000

2550

3150

3650

 

 

218-220

2450

3050

2600

3150

3650

 

222-224

2450

3100

2650

3150

3650

 

 

RTCA unit size

 

 

 

 

 

 

 

108/109/111/208/209/211

2240

1700

1700

-

-

 

113/115/115/213/215/216

2240

2800

2800

-

-

 

 

 

 

 

 

 

 

 

Special Lifting and Moving Instructions

A specific lifting method is recommended as follows:

1.Four lifting points are built into the unit.

2.Slings and spreader bar to be provided by rigger and attached to the four lifting points.

3.Minimum rated lifting capacity (vertical) of each sling and spreader bar shall be no less than the tabulated unit shipping weight.

￿CAUTION

This unit must be lifted with the utmost care. Avoid shock load by lifting slowly and evenly.

￿WARNING

To prevent any damage, position the lifting bar so that the slings do not touch the unit.

Isolation

The most effective form of isolation is to locate the unit away from any sound-sensitive area. Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Spring isolators are not recommended for units equipped with helical rotary compressors. Consult an acoustical engineer in critical sound applications. For maximum isolation effect, isolate water lines and electrical conduit. Wall sleeves and rubber- isolated piping hangers can be used to reduce the sound transmitted through water piping.To reduce the sound transmitted through electrical

conduit, use flexible electrical conduit. State and local codes on sound emissions should always be considered.

Foundation

Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the unit's operating weight (that is, including completed piping, and full operating charges of refrigerant, oil, and water). After it is in place, the unit must be level within 1/4" [6 mm] over its length and width. Use shims if necessary. The manufacturer is not responsible for equipment problems resulting from an improperly designed or constructed foundation.

Note for RTCA:The unit must be positioned so that the airflow through the condensation coils is not hindered by any obstacle.The

10

RLC-SVX03A-E4

Page 10
Image 10
Trane RTCA 108-216, RTUB 207-224 manual Special Lifting and Moving Instructions, Isolation, Foundation