Operation
Pre-start checkout
Installation Checklist
When installation is complete, but prior to putting the unit into service, the following
•Inspect all wiring connections to be sure they are clean and tight.
WARNING
Disconnect all electric power, including remote disconnects, before servicing. Failure to disconnect power before servicing can cause severe personal injury or death.
CAUTION
•Check the tightness of all connections in the compressor power circuit (disconnects, terminal block, contactors, compressor junction box terminals,…). Loose connections can cause overheating at the connections and undervoltage conditions at the compressor motor.
•Open all refrigerant valves in the discharge, liquid, oil, and oil return lines.
CAUTION
Do not operate the unit with the compressor, oil discharge,
•Check the
•Check the unit power phasing L1-
CAUTION
Improper power phasing can result in equipment damage due to reverse rotation.
Do not use untreated or improperly- treated water. Equipment damage may occur.
•Fill the evaporator
The use of
•Close the
•Start the
•With water circulating through the system, adjust the water flow and check the water pressure drop through the evaporator.
•Adjust the
WARNING
Use extreme caution when performing the following procedure with power applied. Failure to do so can result in personal injury or death.
•Reapply power to complete the procedures.
•Prove all Interlock and Interconnecting Wiring Interlock and External as described in the Installation section.
•Check and set, as required, all
•Stop the
•Energize the compressor and oil separators 24 hours prior to unit startup.
Unit Voltage Power Supply Voltage to the unit must meet the criteria given in the Installation section. Measure each leg of the supply voltage at the main power
CAUTION
Provide adequate voltage to the unit. Failure to do so can cause control components to malfunction and shorten the life of relay contact, compressor motors and contactors.
Unit Voltage Imbalance Excessive voltage imbalance between the phases of a
%Imbalance = [(Vx - V ave) x 100]/V ave
V ave = (V1 + V2 + V3)/3
Vx = phase with the greatest difference from V ave (without regard to the sign)
For example, if the three measured voltages are 391, 407, and 402 volts, the average would be:
(391+407+402)/3 = 400
The percentage of the imbalance is then:
This exceeds the maximum allowable (2%) by 0.25%
Unit Voltage Phasing
It is imperative that L1, L2, and L3 in the starter be connected in the
It is important that proper rotation of the compressors be established before the unit is started. Proper
21 |