Installation

Figure 13: RTCA (or other manufacturer's condenser) below the RTUB

3

Limitations: The distance between the two units must not exceed 60 m in reality or the equivalent of 90 m taking into account pressure drops.The height of the liquid line in relation to the condenser base must be less than 5 m.

Legend for Figures 11-12-13:

1 Discharge line connections

2 Liquid line connections 3Trap

4 Counter-trap

18

RLC-SVX03A-E4

Page 18
Image 18
Trane RTCA 108-216, RTUB 207-224 manual Rtca or other manufacturers condenser below the Rtub