Installation

condensation coils must be protected from side winds when their speed exceeds 16 km/h. Position the unit above the average height of snow observed in the region where it is installed. Never install temporary or permanent objects (tarp or roof) over the unit, because recycling of hot air would reduce the capacity of the condensation coils. Discharged air from the fans must not be obstructed. It is prohibited to install ducts for the fan discharge air (even short ones).This is because the fans supplied on standard units do not generate any additional static pressure.

dimensions and recommended clearances. Unobstructed flow of condenser air is essential to maintain chiller capacity and operating efficiency.

Note for RTCA: When determining unit placement, give careful consideration to ensuring a sufficient flow of air across the condenser heat-transfer surface.

Clearances

Provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all service points. Refer to Figure 5 andTable 4 for unit

Figure 5: Unit Dimensions and

Recommended Minimum

Clearances - RTCA

C

A

Figure 6: Unit Dimensions and

Recommended Minimum

Clearances - RTUB

D

B

B

A

D

C

Table 4 - Unit Dimensions and Recommended Minimum Clearances (mm)

 

Length

Width

Height

A

B

C

D

RTCA 108/109/111/208/209/211

2870

2285

1630

1000

1000

1000

1000

RTCA 113/213

4610

2285

1630

1000

1000

1000

1000

RTCA 115/116/215/216

5450

2285

1630

1000

1000

1000

1000

RTUB 207/208

2880

890

1789

950

800

1800

500

RTUB 210/211/212/214/216/217

4150

890

1832

950

800

2750

500

RTUB 218/220

4150

890

1932

950

800

2750

500

RTUB 222/224

4150

890

2041

950

800

2750

500

RLC-SVX03A-E4

11

Page 11
Image 11
Trane RTUB 207-224, RTCA 108-216 manual Clearances, Length Width Height