Trane SCWH, SCRH manual electrical, Installation requirements, Hazardous Voltage

Models: SCWH SCRH

1 36
Download 36 pages 54.67 Kb
Page 20
Image 20
Table I-ER-1. Model SCWH/SCRHelectrical data

electrical

Installation requirements

Table I-ER-1. Model SCWH/SCRHelectrical data

 

 

 

 

 

 

 

 

evaporator standard motor

 

evaporator oversized motor

 

model

tons

voltage

compressor

 

evap. fan motor

min. circuit

MFS / MCB

evap. fan motor

min. circuit

 

MFS /

 

 

 

RLA

LRA

 

qty.

hp

FLA

qty.

ampacity

 

hp

FLA

qty

ampacity

 

MCB

SC*H0303....

 

208-230V/60Hz/3Ph

12.9

77.0

 

 

0.5

2.21

1

18.3

30

 

3.15

 

19.3

 

30

SC*H0304....

3

460V/60Hz/3Ph

5.7

35.0

 

1

 

1.00

 

8.1

15

1

1.42

1

8.5

 

15

SC*H0305....

 

575V/60Hz/3Ph

4.8

31.0

 

 

 

0.80

 

6.8

15

 

1.14

 

7.1

 

15

SC*H0503....

 

208-230V/60Hz/3Ph

22.9

155.0

 

 

 

5.00

 

33.6

50

 

5.81

 

34.4

 

50

SC*H0504....

5

460V/60Hz/3Ph

10.7

75.0

 

1

1

2.50

1

15.9

25

2

2.63

1

16.0

 

25

SC*H0505....

 

575V/60Hz/3Ph

8.5

54.0

 

 

 

1.50

 

12.1

20

 

2.10

 

12.7

 

20

SC*H0753....

 

208-230V/60Hz/3Ph

27.9

164.0

 

 

 

6.30

 

41.2

60

 

5.81

 

40.7

 

60

SC*H0754....

7.5

460V/60Hz/3Ph

13.6

100.0

 

1

2

3.10

1

20.1

30

2

2.63

1

19.6

 

30

SC*H0755....

 

575V/60Hz/3Ph

10.2

78.0

 

 

 

2.40

 

15.2

25

 

2.10

 

14.9

 

25

SC*H1003....

 

208-230V/60Hz/3Ph

22.9

155.0

 

 

 

6.30

 

57.8

80

 

13.70

 

65.2

 

80

SC*H1004....

10

460V/60Hz/3Ph

10.7

75.0

 

2

2

3.10

1

27.2

35

5

6.18

1

30.3

 

40

SC*H1005....

 

575V/60Hz/3Ph

8.5

54.0

 

 

 

2.40

 

21.5

30

 

4.94

 

24.1

 

30

SC*H1203....

 

208-230V/60Hz/3Ph

25.4

147.7

 

 

 

9.40

 

66.5

90

 

13.70

 

70.8

 

90

SC*H1204....

12

460V/60Hz/3Ph

11.8

75.0

 

2

3

4.60

1

31.2

40

5

6.18

1

32.7

 

45

SC*H1205....

 

575V/60Hz/3Ph

9.3

59.6

 

 

 

3.40

 

24.4

30

 

4.94

 

25.9

 

35

SC*H1503....

 

208-230V/60Hz/3Ph

27.9

164.0

 

 

 

9.40

 

72.2

100

 

13.70

 

76.5

 

100

SC*H1504....

15

460V/60Hz/3Ph

13.6

100.0

 

2

3

4.60

1

35.2

45

5

6.18

1

36.8

 

50

SC*H1505....

 

575V/60Hz/3Ph

10.9

78.0

 

 

 

3.40

 

27.9

35

 

4.94

 

29.5

 

35

Notes:

1. Voltage range:

Nominal voltage 208 - 230V - acceptable range: 187 - 253V

Nominal voltage 460V - acceptable range: 414 - 506V

Nominal voltage 575V - acceptable range: 518 - 633V

2.Ampacity is calculated per UL formula, ampacity = (1.25 x compressor RLA + sum of the second compressor RLA (if used) + evaporator motor FLA

3.Maximum fuse size is calculated per UL formula, MFS = (2.25 x compressor RLA) + sum of second compressor RLA (if used) + evaporator motor FLA

Manual background WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

CAUTION

Use Copper Conductors Only! Unit terminals are not designed to accept other type conductors. Failure to use copper conductors may result in equipment damage.

20

PKG-SVX14A-EN

Page 20
Image 20
Trane manual Installation requirements, Hazardous Voltage, Table I-ER-1.Model SCWH/SCRHelectrical data