Trane Service Access, pre-installation Installation considerations, through 7.5-tonSCRH/SCWH

Models: SCWH SCRH

1 36
Download 36 pages 54.67 Kb
Page 7
Image 7
Service Access

pre-installation

Installation considerations

Service Access

3 through 7.5-ton SCRH/SCWH

LATCH

THIS PANEL GOES TO TOP ON

HORIZONTAL AIR DISCHARGE

CONFIGURATION

HEATER

ACCESS

PROVIDED DISASSEMBLED

(FOR FIELD-INSTALLED REAR RETURN)

10 through 15-ton SCWH/SRCH with top-mounted fan configuration

FAN ACCESS

 

 

24"

 

24"

 

 

 

 

COIL / ELECTRIC HEATER

 

 

 

ACCESS

 

 

 

FRONT RETURN

 

 

 

 

MOTOR / DRIVE ACCESS

 

 

 

(RIGHT SIDE)

 

 

CONTROL BOX &

 

 

 

CONDENSER FAN ACCESS

 

 

 

TXV ACCESS

 

 

 

(RIGHT SIDE)

 

AIR FILTER ACCESS

 

UNIT-MOUNTED T-STAT

 

 

 

 

(BOTH SIDES)

 

OPENING (BOTH SIDES)

 

 

 

 

26" SERVICE CLEARANCE

DRAIN CONNECTION

26" SERVICE CLEARANCE

 

RIGHT SIDE

 

 

(BOTH SIDES)

RIGHT SIDE

POWER ENTRY

 

 

 

 

 

(BOTH SIDES)

 

 

 

CONTROL ENTRY

 

 

 

(BOTH SIDES)

 

 

 

 

18" SERVICE CLEARANCE

 

42" SERVICE CLEARANCE FRONT

 

REAR

 

 

26" SERVICE CLEARANCE

REAR RETURN

26" SERVICE CLEARANCE

COMPRESSOR ACCESS

LEFT SIDE

 

 

 

LEFT SIDE

SIGHT GLASS/FILTER DRIER ACCESS (RIGHT SIDE)