Trane SCWH, SCRH manual sequence of, Operation operation, Sequence of Operation

Models: SCWH SCRH

1 36
Download 36 pages 54.67 Kb
Page 24
Image 24
sequence of

sequence of

Operation operation

Sequence of Operation

The thermostat controls the unit operation. It has both manual and automatic switches so the thermostat maintains desired comfort levels.

The fan switch allows manual selection of the fan speed using the On or Auto setting. With the switch set in the On position, the evaporator fan runs continously, independent from the thermostat temperature setting. The Auto position cycles the evaporator fan on and off with the demand for heating or cooling.

The system switch may have two or more positions. For example, using a cooling only thermostat, the system switch can be set in the Off or the Cool position. The Off position disconnects power from the thermostat contacts that control the condensing unit. This prevents

the condensing unit from running, regardless of the thermostat tempera- ture setting. The evaporator fan may circulate air if the fan switch is in the On position. With the switch in the Cool position, the condensing unit and evapo- rator will operate on a signal from the thermostat calling for cooling.

With the fan switch set to Auto and the system switch set to Cool, the following sequence takes place. On a rise in room temperature,t he thermostat contacts close to provide power to the evaporator fan contactor,t he condensing unit fan contactor,a nd the condensingunit compressor contactors. As the room temperature reaches setpoing, the thermostat contacts open to de-energize all contactors,a nd the system cycles off. This system will remain off until additional cooling is required and the cycle repeats.

24

PKG-SVX14A-EN

Page 24
Image 24
Trane SCWH, SCRH manual sequence of, Operation operation, Sequence of Operation