general
Maintenance information
Table M-GI-1. Midrange maintenance general data
| SCWH030 | SCWH050 | SCWH075 | SCWH100 | SCWH120 | SCWH150 |
dimensions, |
|
|
|
|
|
|
height | 66.93 | 78.74 | 78.94 | 91.54 | 95.47 | 95.47 |
length | 31.89 | 36.41 | 40.94 | 65.75 | 65.75 | 80.31 |
depth | 22.24 | 24.01 | 28.74 | 29.52 | 29.52 | 29.52 |
weight (shipping / net) | 494 / 459 | 592 / 555 | 702 / 657 | 1094 / 1027 | 1133 / 1063 | 1249 / 1172 |
cooling performance |
|
|
|
|
|
|
net cooling capacity, btu/h | 36000 | 65290 | 87570 | 116986 | 138204 | 167303 |
EER | 12.13 | 12.28 | 11.6 | 11.5 | 11.1 | 11.3 |
nominal air flow, cfm | 1200 | 2000 | 3000 | 4000 | 4800 | 6000 |
system power, kW | 3.0 | 5.3 | 7.6 | 10.2 | 12.5 | 14.8 |
Copeland scroll compressor |
|
|
|
|
|
|
quantity | 1 | 1 | 1 | 2 | 2 | 2 |
model | ZP32 | ZP57 | ZP83 | ZP57 | ZP67 | ZP83 |
indoor coil, 3/8" tube size |
|
|
|
|
|
|
face area, sq. ft. | 3.19 | 4.98 | 7.13 | 12.12 | 12.12 | 14.56 |
rows / fpf | 4 / 144 | 4 / 144 | 3 / 168 | 2 / 168 | 2 / 168 | 3 / 168 |
water condenser, tube & tube |
|
|
|
|
|
|
water connection, in. | 3/4 NPT | 3/4 NPT | 3/4 NPT | 1 1/4 NPT | 1 1/4 NPT | 1 1/4 NPT |
indoor fan, |
|
|
|
|
|
|
quantity | 1 | 1 | 2 | 2 | 2 | 2 |
diameter x width | 9 x 9 | 10 x 10 | 9 x 9 | 12 x 12 | 12 x 12 | 12 x 12 |
motor | 1 / 0.5 | 1 / 1.0 | 1 / 2.0 | 1 / 2.0 | 1 / 3.0 | 1 / 3.0 |
motor frame size | 56 | 56 | 56 | 56 | 56 | 56 |
air filter, 1" throwaway |
|
|
|
|
|
|
size / (quantity), in. | 14 x 25 (1) | 14 x 20 (1) + | 18 x 24 (2) | 12 x 24 (1) + 24 x 24 (2) | 18 x 24 (3) + | |
|
| 20 x 20 (1) |
|
|
| 24 x 24 (1) |
refrigerant, |
|
|
|
|
|
|
refrigerant charge (Ckt 1 / 2), lbs. | 3.8 | 5.4 | 7.8 | 5.1 / 5.2 | 6.5/6.3 | 7.2/7.2 |
hot water coil, |
|
|
|
|
|
|
face area, sq. ft. | 1.42 | 2.08 | 3.27 | 6.2 | 6.2 | 7.78 |
Notes:
1.Net cooling capacity is rated at 95°F ambient, 80°F entering dry bulb and 67°F entering wet bulb @ SCFM air condition.
2.EER is rated at ARI condition.
25 |