Trane SCRH, SCWH manual Maintenance troubleshooting, Insufficient cooling, Hazardous voltage

Models: SCWH SCRH

1 36
Download 36 pages 54.67 Kb
Page 31
Image 31
Insufficient cooling

Maintenance troubleshooting

Problem

Insufficient cooling

Possible cause

1.Insufficient air flow due to: a) dirty evaporator; b) ice on evaporator coils (indicates airflow restriction through evaporator); c) dirty filter; d) obstructed discharge air intake; e) fan motor not running; f) evaporator fan or fan wheel slipping on motor shaft

2.Heat gain or loss in room exceeds unit capacity

3.Defective compressor

4.Insufficient refrigerant charge indicated

by: a) low wattage; b) condenser air outlet cold

5.Overcharge of refrigerant indicated by high wattage and sweating of the compressor return line

6.Thermostat not set for full cooling

7.Insufficient airflow through condenser

due to: a) dirty condenser; b) loose belt; c) fan loose on shaft

8.Cutout on high pressure

9.Only one refrigerant circuit operational

in 2-circuit units

Manual background WARNING

Hazardous voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious

injury.

Remedy

1.Correct as follows: a) clean; b) defrost (using fan operation only); c) clean or replace filter; d) remove obstruction; e) check electrical system; f) adjust fan position. Tighten set screw on fan wheel.

2.Refer to original load calculations. Recalculate heat gain or loss.

3.Replace, if necessary.

4.Check refrigerant charge pressure with gauges. If refrigerant is low, recharge system.

5.Reclaim excess refrigerant.

6.Refer to thermostat operating instructions.

7.Correct as follows: a) clean coil; b) verify drive is adjusted correctly; c) tighten fan on shaft.

8.See that air is flowing and that damper is set properly.

9.Reset high pressure cutout on inoperative circuit. Check contactor in inoperative circuit.

Problem

Remedy

Unit short cycles

1. Repair or replace.

Possible cause

2. Trace and repair.

1. Remote thermostat

3. Repair or replace.

2. Loose connection in electrical unit

4. Flush or blow dirt out of coil.

3. Thermostat contacts fluttering

5. Reclaim, evacuate, recharge per nameplate.

4.Air flow to evaporator is restricted

5.Insufficient charge

Problem

Remedy

Compressor starts and runs, but fan

1. Replace.

does

2. Replace.

not run.

3. Adjust fan mounting.

Possible cause

 

1.Faulty switch

2.Open fan motor coil circuit

3.Fan binding on shroud or venturi ring

PKG-SVX14A-EN

31

Page 31
Image 31
Trane SCRH, SCWH manual Maintenance troubleshooting, Insufficient cooling, Hazardous voltage