Trane SCWH, SCRH maintenance, Maintenance procedures, Motor Winding Damage, Hazardous Pressures

Models: SCWH SCRH

1 36
Download 36 pages 54.67 Kb
Page 28
Image 28
Motor Winding Damage!

maintenance

Maintenance procedures

CAUTION

Motor Winding Damage!

Do not use a megohm meter or apply greater than 50 VDC to a compressor motor winding while it is under a deep vacuum. Voltage sparkover may cause damage to the motor windings.

Hazardous Pressures! WARNING

Hazardous Pressures!

If a heat source is required to raise the tank pressure during removal of refrigerant from cylinders, use only warm water or heat blankets to raise the tank temperature. Do not exceed a temperature of 150°F. Do not, under any circumstances, apply direct flame to any portion of the cylinder. Failure to follow these safety precautions could result in a violent explosion, which could result in death or serious injury.

Charging the Refrigerant System

To completely charge the system, charge gaseous refrigerant into the suction line shrader valve with the unit running. However, make sure that some refrigerant is present in each circuit before starting the compressors.

CAUTION

Compressor Damage!

Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines may result in compressor damage.

CAUTION

Compressor Damage!

Never manually or automatically pump down below 7 psig. This may cause the compressor to operate in a vacuum and result in compresor damage.

Table M-MP-1. Normal operation condition

 

 

 

 

 

water-cooled

 

air-cooled

 

 

high pressure

 

 

280 to 430 psig

 

320 to 570 psig

 

 

low pressure

 

 

 

100 to 160 psig

 

 

superheat

 

 

 

4 to 9°F

 

 

subcooling

 

 

 

5 to 10°F

Table M-MP-2. Controls adjustment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control

disarming

rearming

 

 

 

 

high pressure control (air-cooled & 12-ton water cooled)

624±17.5 psig

464±29 psig

unit (ton / voltage)

 

 

 

 

 

 

 

high pressure control (water-cooled except 12-ton)

450±10 psig

348±14.5 psig

 

 

 

 

low pressure contol

51±7 psig

94±7 psig

 

 

 

 

 

 

266±5F

194±5

 

3 / 204-230 & 575

 

 

 

275±5F

198

 

5 / 208-230

 

 

 

266±5F

198

 

5 / 575

 

motor windings thermostat, standard motor only

194±5F

135

 

7.5 - 10 / 208-230

 

 

 

248±5F

156

 

7.5 - 10 / 575

 

 

 

194±5F

135

 

12 - 15 / 208-230

 

 

 

221±5F

142

 

12 - 15 / 575

28

PKG-SVX14A-EN

Page 28
Image 28
Trane SCWH maintenance, Maintenance procedures, Motor Winding Damage, Hazardous Pressures, Charging the Refrigerant System