*UD2B060A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
| AIRFLOW | DIP SWITCH SETTING |
|
| EXTERNAL STATIC PRESSURE |
| |||
| SETTING |
|
|
|
|
|
|
|
|
| SW7 | SW8 |
| 0.1 | 0.3 | 0.5 | 0.7 | 0.9 | |
|
|
| |||||||
|
|
|
| CFM | 589 | 604 | 619 | 604 | 607 |
| LOW | ON | ON | TEMP. RISE | 49 | 48 | 47 | 48 | 48 |
|
|
|
| WATTS | 65 | 95 | 125 | 160 | 200 |
|
|
|
|
|
|
|
|
|
|
HEATING |
|
|
| CFM | 663 | 694 | 684 | 681 | 686 |
1ST | MEDIUM ** | ON | OFF | TEMP. RISE | 44 | 42 | 42 | 42 | 42 |
STAGE |
|
|
| WATTS | 75 | 120 | 145 | 185 | 220 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM | 775 | 781 | 776 | 805 | 811 |
| HIGH | OFF | OFF | TEMP. RISE | 37 | 37 | 37 | 36 | 36 |
|
|
|
| WATTS | 105 | 145 | 180 | 230 | 270 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM | 813 | 818 | 818 | 837 | 842 |
| LOW | ON | ON | TEMP. RISE | 55 | 54 | 54 | 53 | 53 |
|
|
|
| WATTS | 110 | 150 | 185 | 240 | 280 |
|
|
|
|
|
|
|
|
|
|
HEATING |
|
|
| CFM | 907 | 919 | 942 | 958 | 959 |
2ND | MEDIUM ** | ON | OFF | TEMP. RISE | 49 | 48 | 47 | 46 | 46 |
STAGE |
|
|
| WATTS | 140 | 200 | 240 | 300 | 330 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM | 1038 | 1066 | 1086 | 1089 | 1079 |
| HIGH | OFF | OFF | TEMP. RISE | 43 | 42 | 41 | 41 | 41 |
|
|
|
| WATTS | 190 | 260 | 325 | 365 | 415 |
|
|
|
|
|
|
|
|
|
|
*UD2B060A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR | AIRFLOW |
| DIP SWITCH SETTING |
|
|
| EXTERNAL STATIC PRESSURE |
| |||||||
UNIT SIZE |
|
|
|
|
| ||||||||||
SETTING |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
(TONS) | SW1 |
| SW2 | SW3 |
| SW4 |
| 0.1 |
| 0.3 | 0.5 | 0.7 |
| 0.9 | |
|
|
|
|
|
| ||||||||||
| LOW | ON |
| ON | OFF |
| ON | CFM | 499 |
| 537 | 520 | 520 |
| 500 |
| (350 CFM/ TON) |
|
| WATTS | 50 |
| 80 | 110 | 145 |
| 175 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.5 | NORMAL | ON |
| ON | OFF |
| OFF | CFM | 605 |
| 610 | 610 | 597 |
| 593 |
(400 CFM/ TON) |
|
| WATTS | 60 |
| 80 | 120 | 155 |
| 180 | |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HIGH | ON |
| ON | ON |
| OFF | CFM | 649 |
| 681 | 665 | 665 |
| 672 |
| (450 CFM/ TON) |
|
| WATTS | 75 |
| 110 | 145 | 180 |
| 220 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LOW | OFF |
| ON | OFF |
| ON | CFM | 680 |
| 722 | 680 | 696 |
| 696 |
| (350 CFM/ TON) |
|
| WATTS | 80 |
| 125 | 150 | 190 |
| 225 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 | NORMAL | OFF |
| ON | OFF |
| OFF | CFM | 798 |
| 804 | 809 | 823 |
| 818 |
(400 CFM/ TON) |
|
| WATTS | 105 |
| 145 | 170 | 235 |
| 280 | |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HIGH | OFF |
| ON | ON |
| OFF | CFM | 884 |
| 896 | 924 | 931 |
| 931 |
| (450 CFM/ TON) |
|
| WATTS | 145 |
| 180 | 240 | 280 |
| 330 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LOW | ON |
| OFF | OFF |
| ON | CFM | 858 |
| 863 | 882 | 894 |
| 895 |
| (350 CFM/ TON) |
|
| WATTS | 125 |
| 175 | 220 | 275 |
| 320 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2.5 | NORMAL | ON |
| OFF | OFF |
| OFF | CFM | 984 |
| 1017 | 1038 | 1017 |
| 1017 |
(400 CFM/ TON) |
|
| WATTS | 170 |
| 225 | 295 | 330 |
| 375 | |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HIGH | ON |
| OFF | ON |
| OFF | CFM | 1125 |
| 1138 | 1150 | 1161 |
| 1161 |
| (450 CFM/ TON) |
|
| WATTS | 245 |
| 315 | 370 | 435 |
| 475 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LOW | OFF |
| OFF | OFF |
| ON | CFM | 1035 |
| 1056 | 1076 | 1076 |
| 1076 |
| (350 CFM/ TON) |
|
| WATTS | 205 |
| 265 | 330 | 370 |
| 430 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 ** | NORMAL ** | OFF |
| OFF | OFF |
| OFF | CFM | 1208 |
| 1247 | 1268 | 1278 |
| 1200 |
(400 CFM/ TON) |
|
| WATTS | 300 |
| 360 | 440 | 485 |
| 490 | |||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HIGH | OFF |
| OFF | ON |
| OFF | CFM | 1380 |
| 1410 | 1402 | 1350 |
| 1235 |
| (450 CFM/ TON) |
|
| WATTS | 440 |
| 500 | 550 | 550 |
| 525 | ||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTES:
1.*FIRST LETTER MAY BE "A" OR "T"
2.**FACTORY SETTING.
3.CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.
4.LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.
DATA SUBJECT TO CHANGE WITHOUT NOTICE | 9 |