Features (Rear Panel) continued

23.Input Voltage Select Switch (6kVA and 10kVA models only): Use this switch to set the transformer module's input voltage (either 200V AC, 208V AC or 240V AC). See “Connection” section for details.

24.AC Output Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA 5-15P or NEMA 5-20P equipment plugs.

25.AC Output Breakers (5kVA models only): Push-button breakers control output power to transformer module's AC Output Receptacles which are directly adjacent.

26.Cable for Power Module Connection (5kVA models only): Plugs directly into either of the 5kVA power module's AC Output 2

Receptacles. NOTE: this cable should only be plugged into the 5kVA power module.

Battery Module Feature Description

27. Input Connector (select Battery Modules only): Use this connector to daisy chain additional battery modules onto the first. Remove the cover panel for access. Refer to the battery module owner’s manual for connection instructions and safety warnings.

28. Output Cable: Use this cable to connect the battery module to the power module or to another battery module. The power module will not start without a connection to a charged battery module. Refer to the battery module owner’s manual for connection instructions and safety warnings.

Connection

Hardwiring Cautions (6kVA & 10kVA models only)

Wiring must be done by a qualified electrician.

The UPS power module may be installed on its own or connected to an isolation transformer module. Both applications require the power module to be connected to a battery module.

When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC) in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS’s

AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 24-28 inch-pounds (2.7-3.2 NM).

Make sure that your equipment is properly grounded.

Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to make wiring connections (Ground conductors must be the same size and type as the power conductors used):

 

RATED INPUT CURRENT

RATED OUTPUT CURRENT

RATED OUTPUT CURRENT

OUTPUT PROTECTION

 

200 - 240 (1Ø, 2-Wire + PE)

200 - 240V (1Ø, 2-Wire + PE)

120V (1Ø, 2-Wire + PE)

CIRCUIT

6kVA Models

30A 8 AWG (10mm2)

30A 8 AWG (10mm2)

2 × 30A 8 AWG (10mm2)

30A

10kVA Models

50A 6 AWG (16mm2)

50A 6 AWG (16mm2)

2 × 50A 6 AWG (16mm2)

63A

Connecting Modules to Each Other and to Utility Power and Equipment

There are three separate UPS system modules available from Tripp Lite (a power module and a battery module, which are required in all applications, and a transformer module) used in a variety of combinations. Follow the connection procedure below which matches the combi- nation of modules which you plan on installing.

10

Page 10
Image 10
Tripp Lite 10KVA owner manual Connection, Battery Module Feature Description

10KVA specifications

The Tripp Lite 10KVA is a highly versatile and robust uninterruptible power supply (UPS) system designed to provide seamless power protection for critical applications. This unit is ideal for data centers, telecommunications equipment, and industrial applications where power stability is paramount. With a rated capacity of 10,000 VA, it ensures that your equipment remains operational during power outages or fluctuations.

One of the key features of the Tripp Lite 10KVA is its advanced battery management system. This technology not only prolongs the life of the batteries but also optimizes their performance. The UPS comes equipped with high-capacity batteries, allowing for extended backup times and ensuring that connected devices can function uninterrupted during emergencies.

Another notable feature is the inverter efficiency, which allows the UPS to convert stored battery power into reliable AC output with minimal loss. This is critical in high-demand scenarios where energy efficiency is essential. The Tripp Lite 10KVA also boasts a wide input voltage range and frequency compatibility, making it suitable for various electrical environments.

The unit incorporates multiple outlets, providing the flexibility to connect diverse devices simultaneously. Additionally, the Tripp Lite 10KVA includes an LCD display, offering real-time data on battery status, load levels, and operating conditions, which aids in proactive management of power resources.

For enhanced safety, the UPS is equipped with numerous protection features, including surge suppression, which protects sensitive equipment from voltage spikes. It also includes built-in circuit breakers to prevent overloads and short circuits, ensuring the safety of both the UPS and connected devices.

Networking capabilities are another standout characteristic of the Tripp Lite 10KVA. With optional SNMP support, users can monitor the UPS remotely, allowing for effective management and troubleshooting from virtually anywhere. This feature enhances system reliability and contributes to a more efficient operational workflow.

In conclusion, the Tripp Lite 10KVA is a powerful and reliable UPS solution that combines advanced technologies with thoughtful features to deliver unmatched performance. Its robust design, efficiency, and extensive safety measures make it a vital component for any organization looking to safeguard their critical power infrastructure. Whether for business continuity or equipment protection, the Tripp Lite 10KVA stands out as a premier choice in the UPS market.