Connection Combination #4:

Connection continued

Connection Combination #4:

Power Module (6kVA) + Transformer Module (6kVA) + Battery Module(s)

1Connect the power module to the transformer module.

Using a screwdriver, remove the entire box A covering the power module’s input and output terminals. Remove the screws on either side of the terminals. Grip the terminals B and slide them out until you can view the cable connector release tab C . Press the tab down and pull on the cables to release them from the internal connector D . Remove the terminals. Insert the connector cable

from the transformer module E into the internal connectors in the power module’s terminal box until the release tab clicks in place. Replace the screws around the plate. Although they are not needed, retain the power module’s terminals and terminal box cover in case you plan to operate the power module without the transformer module at a future date.

2Hardwire the transformer module to your equipment.

Using a screwdriver, remove the top of the box F covering the transformer module’s input and output terminals. Pass a user-supplied cable through the box’s left knockout G and connect it to the transformer module’s output ter- minals. See the AC Output Voltage Diagram H to determine which terminal connections will provide voltage appropriate to your application. Connect the other end of the cable to your equipment.

A

 

D

B

C

1

 

 

 

NORMAL

 

BY

 

PASS

1

E

 

F

 

NORMAL

 

BY

 

PASS

 

G

2

 

3Hardwire the transformer module to a utility

power source.

Pass a user-supplied cable through the box’s right knockout I and connect it to the transformer module’s input terminals. Replace the top of the box covering the transformer module’s terminals. Connect the other end of the cable to a utility power source.

Connection Combination #4 continued on next page
AC OUTPUT VOLTAGE DIAGRAM

 

208V

 

240V

120V

120V

 

G

H

 

 

NORMAL

 

BY

 

PASS

3

I

 

14

Page 14
Image 14
Tripp Lite 10KVA owner manual Connection Combination #4, Power Module 6kVA + Transformer Module 6kVA + Battery Modules