Tripp Lite 10KVA owner manual Power ON/OFF 5kVA models only, 5kVA Models Front Panel

Models: 10KVA

1 96
Download 96 pages 30.32 Kb
Page 18
Image 18
Power ON/OFF (5kVA models only)
Display D

Power ON/OFF (5kVA models only)

1.To put UPS in BYPASS mode: Press and hold the OFF button F until the UPS beeps once.

Put the UPS in SETUP mode by holding down the SCROLL A and SELECT B buttons simultaneously.

Scroll through setup options (using A or B ) and select the appropriate setting for each of the following options using the SELECT button B .

a.Output Voltage: Select 200, 208, 220, 230 or 240V AC..

b.Output Frequency: Your UPS will auto-select 50 or 60 Hz to match the input.

c.Economy Mode: Your UPS can provide on-line operation with zero transfer-time. It can also operate in a more energy- efficient, line-interactive mode. Select “Economy On” to put the UPS in line-interactive mode. Select “Economy Off” to put the UPS in on-line mode.

After you have set these options, exit the SETUP mode with the SCROLL button A then exit BYPASS mode by holding down the ON button C until you hear the UPS beep once.

2.Turn input to the UPS ON: Press and hold the power module's ON button C until you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS. Your UPS will perform a brief self-test and show the results on the LCD Display D . See "Startup Self-Test" in the "Operation" section for the display sequence.

3. To turn the UPS power module and transformer module (if used) OFF: Press the power module's OFF button F until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display D will show BYPASS MODE. Turn the power module's Output Breaker E OFF. Unplug the power module's AC input cord from the wall outlet. If a transformer module is used, unplug its connector cable from the power module. Your load will no longer be energized, and the LCD

5kVA Models will be dark.

E

5kVA Models

 

 

 

D

C

A

B

F

5kVA Models (Front Panel)

18

Page 18
Image 18
Tripp Lite 10KVA owner manual Power ON/OFF 5kVA models only, 5kVA Models Front Panel