Image 12
6Turn input to the UPS ON

Connection continued

6Turn input to the UPS ON

If the UPS is connected to a transformer, turn the transformer’s UPS and Load Breakers ON.

Turn the UPS’s Input Circuit Breaker ON.

Press the UPS’s ON button until you hear a beep to begin inverter operation.

If your AC input is not providing power normally, you may “cold start” your UPS from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold the “ON” switch until you hear a beep to start your UPS in “ON BATTERY” mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS.

Your UPS will perform a brief self-test and show the results on the LCD Display. See the Self-Test section, pg. 12, for the display sequence.

7Configure your UPS’s output.

Put your UPS into bypass mode by holding the OFF button down until the UPS beeps, then put your UPS into setup mode by holding down both of its scroll buttons at once. Scroll through the setup options and select the appropriate setting for each of the following options.

Output Voltage: Select 200, 208, 220, 230 or 240 VAC.

Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.

Economy Mode: Your UPS can provide on-line operation with zero transfer time. It can also operate in a more energy-efficient line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put the UPS in on-line mode.

After you have set these options, exit the setup mode with the scroll buttons, then exit bypass mode by holding the ON button down until you hear a beep.

8Turn UPS output ON.

Turn the UPS’s Output Circuit Breaker ON.

If the UPS is connected to a transformer, turn the transformer’s Manual Bypass Switch from BYPASS to NORMAL.

Your UPS will now provide power to connected equipment.

9To turn the UPS and transformer OFF.

Press the UPS’s OFF button until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display will show “BYPASS MODE.”

Turn the UPS’s Input and Output Circuit Breakers OFF. If the UPS is connected to a transformer, turn the transformer’s AC Input and Output Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.