Specifications
Specifications are for UPS, Isolation Transformer, and one battery pack.
Model | SU6000RT3U | SU10KRT3U | |
Input |
|
| |
UPS Input Voltage | 156V~276V Single Phase | 156V~276V Single Phase | |
Transformer Input Voltage | 200/208/220/230/240V | 200/208/220/230/240V | |
Input Frequency | 50/60 Hz ± 3 Hz | 50/60 Hz ± 3 Hz | |
Input Current | 22.6A | 40A | |
Inrush Current | <150A | <200A | |
Power Factor (Full Load) | >0.97 | >0.97 | |
Efficiency (Full | >87% | >88% | |
UPS Circuit Breaker | 40A | 63A | |
Transformer Circuit Breaker | 40A (2 pole) | 63A (2 pole) | |
Output |
|
| |
VA | 6000 | 10000 | |
Watts (Power Factor: 0.7) | 4200 | 7000 | |
Waveform | Sinewave | Sinewave | |
Waveform | Sinewave | Sinewave | |
Output Voltage (RMS) | 120/200/208/220/230/240V | 120/200/208/220/230/240V | |
Output Frequency | 50/60 Hz | 50/60 Hz | |
|
| (± 0.2 Hz on battery) | (± 0.2 Hz on battery) |
Voltage Regulation | ±3% | ±3% | |
Max. Harmonic Distortion |
|
| |
| (Linear Full Load) | <3% | <3% |
| <6% | <6% | |
Overload Capabilities | 102% (continuous) | 102% (continuous) | |
|
| 102%~125% (1 min.) | 102%~125% (1 min.) |
|
| 125%~150% (30 sec.) | 125%~150% (30 sec.) |
|
| >150% (Immediate) | >150% (Immediate) |
Short Circuit Capability | 90A* | 160A* | |
UPS Circuit Breaker | 40A | 63A | |
Transformer Circuit Breaker | 30A (3 pole) | 63A (3 pole) | |
Crest Factor | 3:1 | 3:1 |
*The short circuit capability at 1ø 2W 120V for the SU6000RT3U is greater than 180A, and for the SU10KRT3U is greater than 320A.
Operation |
|
|
|
| |
(Line to Battery, Battery to Line) | 0 ms | 0 ms |
Audible Noise (Full Load @ 1 m) | <50 dBA | <55 dBA |
Typical Backup Time (Single Battery Pack) |
|
|
(Full Load) | 10 min. | 6 min. |
(Half Load) | 25 min. | 15 min. |
Indicators
Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).
Communications
Includes an
Physical Specifications |
|
|
(H × D × W) | 51/8 × 17½ × 22½ in. | 51/8 × 17½ × 22½ in. |
| (13 × 45 × 58 cm.) | (13 × 45 × 58 cm.) |
Net Weight (UPS) | 42 lb. (19.1 kg) | 53 lb. (24.1 kg) |
Net Weight (Transformer) | 120 lb. (54.5 kg) | 120 lb. (54.5 kg) |
Net Weight (Battery Pack) | 170 lb. (77.3 kg) | 170 lb. (77.3 kg) |
17 |