Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline Rackmount UPS Systems and their batteries.
UPS Location Warnings
•Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
•Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
•Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures between 62° F and 84° F (between 17° C and 29° C).
•Leave adequate space around all sides of the UPS for proper ventilation: 12 in. (30 cm.) clearance at the rear; 4 in. (10 cm.) at sides and on top.
•Do not install the UPS near magnetic storage media, as this may result in data corruption.
UPS Connection Warnings
• The power supply for this unit must be single phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
Equipment Connection Warnings
•Do not use Tripp Lite UPS Systems in life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device.
•Connect your UPS’s and/or isolation transformer’s grounding terminal to a grounding electrode conductor.
•The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
Maintenance Warnings
•Your UPS, transformer and battery pack(s) do not require routine maintenance. Do not open them for any reason. There are no
Battery Warnings
•Do not operate your UPS without connecting it to an external battery pack.
•Connect only Tripp Lite battery packs to your UPS’s external battery connector.
•The batteries in your battery pack are recyclable. Refer to local codes for disposal requirements, or if in the USA call
•Because the batteries present a risk of electrical shock and burn from high
•Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
•Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
•Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed via the transformer (see pg.
•Do not connect or disconnect battery pack(s) while the UPS is operating from the battery supply or when the transformer is not in bypass mode.
•During