Specifications

 

MODEL NUMBER:

EMS1012UL

EMS1250UL

EMS2012UL

 

Series Number:

AGAP100012MV3

AGAP5094

AGAP200012MV3

 

 

 

 

 

 

AC Input Connection:

Input Cord

Input Cord

Hardwire

 

 

 

 

 

 

INVERTER

 

 

 

 

 

 

 

 

 

Common Specifications for All Models • DC Input Volts (Nominal): 12 VDC • DC Input Voltage Range: 10 - 15 VDC

• Output Volts (Nominal): 120 VAC, ± 5%

• Output Frequency (Nominal): 60 Hz, ± 0.5%

 

• Efficiency: 88% to 94% depending on load and temperature

 

 

 

Tripp Lite Inverter/Chargers include a Battery Charge Conserver (Load Sense) Control which saves battery power by allowing users to set the minimum load level at which the unit’s inverter turns on. Users can significantly reduce the No Load DC Input Current (approximately 1 A to 3 A for all models) to a very low amp level with the use of this control.

 

Continuous Power (@ 20 C):

1000

1250

2000

 

OverPower™ Peak Surge Power:*

1500

1875

3000

 

 

 

 

 

 

Double Boost™ Peak Surge Power:*

2000

2500

4000

 

 

 

 

 

 

Maximum Output AC Current (Continuous):

8.3 A

10.4 A

16.7 A

 

 

 

 

 

 

UL-Recognized DC Fuse Required:

200 A

200 A

400 A

 

 

 

 

 

 

DC Input Current @ Nominal V DC

 

 

 

 

Full Load

95 A

127 A

190 A

 

 

 

 

 

 

BATTERY CHARGER

 

 

 

 

 

 

 

 

 

Common Specifications for All Models • Acceptance Volts VDC: Selectable 14.4 V** / 14.2 V Wet** / Gel

• Float Volts DC (w/gel): 13.3 V (13.6 V)

• Input Volts (Nominal): 120 VAC

 

Charging Capacity DC:

55 A**/14 A

55 A** / 14 A

100 A**/25 A

 

 

 

 

 

 

Input Current AC:

11.5 A

11 A

20A

LINE VAC OPERATION

 

Common Specifications for All Models • Minimum Input Volts (Transfer to Battery): Selectable 75,** 85, 95 or 105 VAC

• Maximum Input Volts (Transfer to Battery): Selectable 135** or 145 VAC • Input

 

Frequency (Nominal): 60 Hz, ±10%

 

 

 

 

 

 

 

 

 

Maximum Input AC Current (Continuous, Charger at Maximum):

12 A

12 A

38 A

 

 

 

 

 

 

Maximum Bypass AC Current (load circuit breaker limited):

12 A

12 A

20 A

*OverPower duration (up to 1 hour). DoubleBoost duration (up to 10 seconds). Actual duration depends on battery age, battery charge level and ambient temperature. **Factory setting. Not applicable to Model EMS1250UL; switches select Charger Enable/Charger Inhibit. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

Minimum Recommended Cable Sizing Chart*

Use in conjunction with DC wiring connection instructions in the Battery Connection section.

 

 

Inverter/Charger DC Volt: 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire Gauge

 

 

 

 

 

 

 

 

 

 

 

 

Watts

6

4

 

2

 

0

00 (2/0)

 

500

15 ft

25 ft

 

39 ft

 

62 ft

79 ft

 

700

11 ft

18 ft

 

28 ft

 

44 ft

56 ft

 

1000

N/R

12 ft

 

20 ft

 

31 ft

39 ft

2000

N/R

N/R

 

N/R

 

16 ft

20 ft

 

 

 

 

 

 

 

 

 

 

2400

N/R

N/R

 

N/R

 

13 ft

16 ft

 

3000

N/R

N/R

 

N/R

 

10 ft

13 ft

* N/R = Not Recommended. NOTE: Acceptable power is directly related to cable length (i.e. the shorter the cable, the better the performance)

Note on Labeling Two symbols are used on the EMS labels. V~: AC Voltage V : DC Voltage

200412021 93-2404

Page 13
Image 13