Basic Operation continued

Other UPS Features (Rear Panel)

15A 120V

NEMA 5-15R

20A 120V

NEMA 5-20R

AC Outlets: All models include NEMA 5-15R and/or NEMA

5-20R outlets. Select models also include NEMA L5-30R and/or NEMA L5-20R outlets. These outlets provide your connected equipment with AC line power during normal operation and battery power during blackouts and brownouts. The UPS protects equipment connected to these outlets against damaging surges and line noise. If you have a serial or USB connection to your UPS, you can remotely reboot connected equipment by turning the outlets OFF and ON using Tripp Lite’s PowerAlert Software. The outlets are divided into one or more load banks (labelled “LOAD 1,” etc.) which may be remotely switched OFF and ON without interrupting power to equipment connected to the other outlets. Outlets labelled “UNSWITCHED” may not be remotely switched off.

30A

120V

20A

120V

NEMA

L5-30R

NEMA

L5-20R

Communications Ports (USB or RS-232): These ports connect your UPS to any workstation or server. Use with Tripp Lite’s PowerAlert Software and included cables to enable your computer to automatically save open files and shut down equipment during a blackout. Also use PowerAlert Software to monitor a wide variety of AC line power and UPS operating conditions. Consult your PowerAlert Software manual or contact Tripp Lite Customer Support for more information. See “USB and RS-232 Serial Communications” in the “Optional Installation” section for installation instructions.

EPO (Emergency Power Off) Port: Your UPS features a EPO port that may be used to connect the UPS to a contact closure switch to enable emergency inverter shutdown. See Optional Installation.

Accessory Slot: Remove the small cover panel from this slot to install optional accessories to remotely monitor and control your UPS. Refer to your accessory’s manual for installation instructions. Contact Tripp Lite Customer Support at www.tripplite.com/support for more information, including a list of available SNMP, network management and connectivity products.

External Battery Connector (optional on select models): Use to connect Tripp Lite external battery packs for additional runtime. Refer to instructions available with the battery pack for complete connection information and safety warnings. Visit www.tripplite.com/support/battery/index.cfm to locate the supported battery type(s) for your UPS.

16

12-12-037-93-3088-B.indb 16

12/26/2012 3:47:34 PM

Page 16
Image 16
Tripp Lite SMART2200RMXL2UP Other UPS Features Rear Panel, AC Outlets All models include Nema 5-15R and/or Nema