Storage

First turn your UPS OFF: press the “OFF” switch to turn power off at the UPS out- lets, then disconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery drain. If you plan on storing your UPS for an extend- ed period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period of time, they may suffer permanent loss of capacity.

Service

If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIG- INAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.

Specifications

All Models: Input Frequency (50/60 Hz Auto-Selecting); Output Waveform in Line and Battery Modes (Pure Sine Wave); Transfer

Time: (0 ns.); Maximum Harmonic Distortion with Linear Load (< 3%); Maximum Harmonic Distortion with Nonlinear Load (< 6%); Battery Recharge Time to 80% Capacity (2-4 hours).

Model

SU1000RT2U

SU1000RT2UHV

Input Voltage:

120V

200/208/240V

Input Breaker Rating:

15A

8A

Input Plug Type:

5-15P

6-15P

Recommended Utility Amps:

15A

15A

Output Capacity (VA/Watts):

1000/800

1000/800

Battery Runtime (Half Load/Full Load) Min.:

18/6

18/6

System Battery Voltage:

36 VDC

36 VDC

Approvals:

UL, cUL, FCC, NOM

UL, cUL, FCC, NOM

Model

SUINT1000RT2U

SU2200RT2U

Input Voltage:

220/230/240V

120V

Input Breaker Rating:

8A

30A

Input Plug Type:

IEC 320-C14

5-20P

Recommended Utility Amps:

10A

20A

Output Capacity (VA/Watts):

1000/800

2200/1600

Battery Runtime (Half Load/Full Load) Min.:

18/6

18/6

System Battery Voltage:

36 VDC

72 VDC

Approvals:

CE

UL, cUL, FCC, NOM

Model

SU2200RT2UHV

SUINT2200RT2U

Input Voltage:

200/208/240V

220/230/240V

Input Breaker Rating:

15A

15A

Input Plug Type:

6-20P

IEC 320-C20

Recommended Utility Amps:

20A

20A

Output Capacity (VA/Watts):

2200/1600

2200/1600

Battery Runtime (Half Load/Full Load) Min.:

18/6

18/6

System Battery Voltage:

48 VDC

48 VDC

Approvals:

UL, cUL, FCC, NOM

CE