Tripp Lite SU5000RT4U, SU8000RT4U, SU6000RT4U owner manual Overload Messages, Bypass Messages

Models: SU5000RT4U SU6000RT4U SU8000RT4U

1 52
Download 52 pages 59.76 Kb
Page 14
Image 14
Overload Messages

Operation (continued)

Overload Messages

When the UPS detects an output overload, its LCD will switch to the following display:

OVERLOAD!

LOAD1 = XXX% X.XKW

OVERLOAD!

LOAD2 = XXX% X.XKW

The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to BYPASS MODE to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:

Overload Condition

Countdown Duration

102% - 125%

1 minute

 

 

125% - 150%

30 seconds

> 150%

Immediate Bypass

 

 

Bypass Messages

While in BYPASS MODE, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in BYPASS MODE. If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load.

Bypass Voltage Conditions

LCD Screen Messages

L1 > 15% Higher

BYPASS AC1 HIGH

 

Than Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 > 15% Higher

 

 

BYPASS AC2 HIGH

 

Than Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L1 > 20% Lower

 

 

BYPASS AC1 LOW

 

Than Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 > 20% Lower

 

 

BYPASS AC2 LOW

 

Than Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

 

L1 Voltage Was Too High,

BYPASS AC1 WAS HI

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

 

L2 Voltage Was Too High,

BYPASS AC2 WAS HI

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

 

L1 Voltage Was Too Low,

BYPASS AC1 WAS LO

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

 

 

 

L2 Voltage Was Too Low,

BYPASS AC2 WAS LO

 

Now Returned to Nominal Voltage

LOAD1 = XXX% X.XKW

 

 

 

 

14

201102170 932611.indd 14

3/30/2011 10:22:17 AM

Page 14
Image 14
Tripp Lite SU5000RT4U Overload Messages, Bypass Messages, OVERLOAD LOAD1 = XXX% X.XKW OVERLOAD LOAD2 = XXX% X.XKW