Operation (continued)

Shutdown Messages

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Shutdown Conditions

LCD Screen Messages

L1 Extended Overload

SHUTDOWN

L1 OVERLOAD=XXX%

 

 

 

 

 

L2 Extended Overload

SHUTDOWN

L2 OVERLOAD=XXX%

 

 

 

L1 to L2

 

OP SHORTCIRCUIT

Output Short Circuit

LOAD1 = XXX% X.XKW

 

 

 

 

L1 to N Output Short Circuit

OP1 SHORTCIRCUIT

LOAD1 = XXX% X.XKW

 

 

 

 

 

L2 to N Output Short Circuit

OP2 SHORTCIRCUIT

LOAD1 = XXX% X.XKW

 

 

 

 

 

Remote Shutdown Command

REMOTE COMMAND

(via DB9)

LOAD1 = XXX% X.XKW

 

 

Remote Shutdown Command

 

EMERGENCY STOP!

(via EPO)

LOAD1 = XXX% X.XKW

 

 

 

 

Battery Depletion

LOW BATTERY

LOAD1 = XXX% X.XKW

 

 

 

 

 

Site Wiring Fault

SITE WIRING FAULT

LOAD1 = XXX% X.XKW

 

 

 

 

 

EEPROM Failure

EEPROM FAIL

LOAD1 = XXX% X.XKW

 

 

 

 

 

Positive DC BUS Voltage

+DC BUS HIGH

is Too High

LOAD1 = XXX% X.XKW

 

 

 

 

Positive DC BUS Voltage

+DC BUS LOW

is Too Low

LOAD1 = XXX% X.XKW

 

 

Negative DC BUS Voltage

 

-DC BUS HIGH

is Too High

LOAD1 = XXX% X.XKW

 

 

 

 

Negative DC BUS Voltage

-DC BUS LOW

is Too Low

LOAD1 = XXX% X.XKW

 

 

 

 

Fan Failure

FAN FAIL

LOAD1 = XXX% X.XKW

 

 

 

 

 

UPS Overtemperature

OVERTEMPERATURE

LOAD1 = XXX% X.XKW

 

 

 

 

 

L1 Inverter Too High

INVERTER1 HIGH

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L1 Inverter Too Low

INVERTER1 LOW

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 Inverter Too High

INVERTER2 HIGH

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 Inverter Too Low

INVERTER2 LOW

LOAD1 = XXX% X.XKW

 

 

 

Shutdown Conditions

LCD Screen Messages

Internal Charger Failure

INT CHARGER

FAIL

LOAD1 = XXX%

X.XKW

 

 

 

 

 

 

 

External Charger Failure

EXT CHARGER

FAIL

LOAD1 = XXX%

X.XKW

 

 

 

 

 

 

Battery Open / Bad Battery

BAD BATTERY!

LOAD1 = XXX%

X.XKW

 

 

 

Phase Lock Failure,

 

 

BYPASS LOCKOUT

Bypass Lockout

LOAD1 = XXX%

X.XKW

 

 

Phase Lock Failure,

 

INVERTER LOCKOUT

Inverter Lockout

LOAD1 = XXX%

X.XKW

15

201102170 932611.indd 15

3/30/2011 10:22:18 AM

Page 15
Image 15
Tripp Lite SU8000RT4U, SU6000RT4U, SU5000RT4U owner manual Shutdown Messages, OP2 Shortcircuit

SU5000RT4U, SU6000RT4U, SU8000RT4U specifications

Tripp Lite is a renowned name in the realm of power protection solutions, and their line of uninterruptible power supplies (UPS) stands out for providing superior performance and advanced features. The Tripp Lite SU6000RT4U, SU5000RT4U, and SU8000RT4U are all remarkable options designed for various applications, ensuring consistent power delivery and robust protection against electrical disturbances.

The SU6000RT4U is a 6000VA/5400W UPS system that offers exceptional reliability to safeguard your critical equipment. It features a dual-conversion online design, which guarantees a steady output voltage regardless of fluctuations in input power. The hot-swappable batteries allow for uninterrupted power, ensuring that maintenance can occur without downtime. The graphical LCD display provides real-time information about UPS status, input/output voltage, and battery condition, enabling users to monitor performance effortlessly.

Next in line, the SU5000RT4U offers a 5000VA/4500W capacity and similar technological advancements. This model is engineered to support high-sensitive equipment, making it perfect for data centers, networking devices, and other critical applications. It includes advanced surge protection, ensuring that any spikes in electricity do not cause damage to connected devices. Like the SU6000RT4U, it also employs a dual-conversion design for superior power quality.

The SU8000RT4U is an impressive 8000VA/7200W UPS that caters to demanding applications. In addition to the features found in the smaller models, it boasts an extensive runtime, allowing it to sustain operations during prolonged power outages. This model also supports advanced management options, such as SNMP networking capabilities, which grants users the ability to monitor and manage the UPS remotely via any networked device. The battery management technology extends battery life and enhances performance, making it a standout choice for high-efficiency environments.

All three Tripp Lite UPS units are designed with foolproof safety measures, including automatic voltage regulation, isolating transformers, and thermal protection to promote longevity and reliability. Built with a rugged metal housing, they ensure durability in a variety of conditions. Compact and rack-mountable, these UPS systems fit seamlessly into data racks or server environments. With their robust features, the SU6000RT4U, SU5000RT4U, and SU8000RT4U ensure that your valuable equipment is always protected from the unpredictability of power supply issues.