Tripp Lite SU8000RT4U, SU6000RT4U Shutdown Messages, Remote Command, Low Battery, Overtemperature

Models: SU5000RT4U SU6000RT4U SU8000RT4U

1 52
Download 52 pages 59.76 Kb
Page 15
Image 15
Shutdown Messages

Operation (continued)

Shutdown Messages

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Shutdown Conditions

LCD Screen Messages

L1 Extended Overload

SHUTDOWN

L1 OVERLOAD=XXX%

 

 

 

 

 

L2 Extended Overload

SHUTDOWN

L2 OVERLOAD=XXX%

 

 

 

L1 to L2

 

OP SHORTCIRCUIT

Output Short Circuit

LOAD1 = XXX% X.XKW

 

 

 

 

L1 to N Output Short Circuit

OP1 SHORTCIRCUIT

LOAD1 = XXX% X.XKW

 

 

 

 

 

L2 to N Output Short Circuit

OP2 SHORTCIRCUIT

LOAD1 = XXX% X.XKW

 

 

 

 

 

Remote Shutdown Command

REMOTE COMMAND

(via DB9)

LOAD1 = XXX% X.XKW

 

 

Remote Shutdown Command

 

EMERGENCY STOP!

(via EPO)

LOAD1 = XXX% X.XKW

 

 

 

 

Battery Depletion

LOW BATTERY

LOAD1 = XXX% X.XKW

 

 

 

 

 

Site Wiring Fault

SITE WIRING FAULT

LOAD1 = XXX% X.XKW

 

 

 

 

 

EEPROM Failure

EEPROM FAIL

LOAD1 = XXX% X.XKW

 

 

 

 

 

Positive DC BUS Voltage

+DC BUS HIGH

is Too High

LOAD1 = XXX% X.XKW

 

 

 

 

Positive DC BUS Voltage

+DC BUS LOW

is Too Low

LOAD1 = XXX% X.XKW

 

 

Negative DC BUS Voltage

 

-DC BUS HIGH

is Too High

LOAD1 = XXX% X.XKW

 

 

 

 

Negative DC BUS Voltage

-DC BUS LOW

is Too Low

LOAD1 = XXX% X.XKW

 

 

 

 

Fan Failure

FAN FAIL

LOAD1 = XXX% X.XKW

 

 

 

 

 

UPS Overtemperature

OVERTEMPERATURE

LOAD1 = XXX% X.XKW

 

 

 

 

 

L1 Inverter Too High

INVERTER1 HIGH

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L1 Inverter Too Low

INVERTER1 LOW

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 Inverter Too High

INVERTER2 HIGH

LOAD1 = XXX% X.XKW

 

 

 

 

 

 

 

L2 Inverter Too Low

INVERTER2 LOW

LOAD1 = XXX% X.XKW

 

 

 

Shutdown Conditions

LCD Screen Messages

Internal Charger Failure

INT CHARGER

FAIL

LOAD1 = XXX%

X.XKW

 

 

 

 

 

 

 

External Charger Failure

EXT CHARGER

FAIL

LOAD1 = XXX%

X.XKW

 

 

 

 

 

 

Battery Open / Bad Battery

BAD BATTERY!

LOAD1 = XXX%

X.XKW

 

 

 

Phase Lock Failure,

 

 

BYPASS LOCKOUT

Bypass Lockout

LOAD1 = XXX%

X.XKW

 

 

Phase Lock Failure,

 

INVERTER LOCKOUT

Inverter Lockout

LOAD1 = XXX%

X.XKW

15