LCD DISPLAY SELECT SWITCH

Momentarily press the "SELECT" switch on the front panel to browse through different power readings on the LCD Display. The LCD Display will show which one of four operational modes your UPS is currently in: Normal, Economy, On-Battery, or Bypass. Also, a syou press the "SELECT"switch, the LCD Display will browse through load. input, bypass, output and battery conditions.

"NORMAL"MODE OPERATION "ON-BATTERY" MODE OPERATION

"ECONOMY'MODE OPERATION "ON BYPASS" MODE OPERATION

OPERATION ON BYPASS-VOLTAGE OUT OF RANGE

While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltagepasses out of an acceptable range (between 15%higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level. the UPS resumes supplying power to the load, and its LCD reports that output voltagewas too high or too low a t one time, but has returned to nominal.

Bypass Voltage Condition

LCD Display Message

>15Oh Higher than Nominal

BYPASS AC TOO HI

>20% Lower than Nominal

BYPASS AC TOO M

Was Too High. Now Nominal

BYPASS AC WAS HI

Was Too Low. Now Nominal

BYPASS AC WAS LO

OPERATION ON OVERLOAD

When the UPS detects an output overload, it will commence a countdown (the length of time depending on the severity of the overload). If the UPS is still overloaded a t the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.

Overload Condition

LCD Display Message

Countdown to Shutdown

102%

- 125%

Overload 102%

1 minute

 

 

Load=XXXOhX.XXKW

 

125%

- 150%

Overload 125%

30 seconds

 

 

Load=XXXOh XXXKW

 

>150%

Overload 150%

2 seconds

 

 

Load=XXXOhX.XXKW

 

11

Page 11
Image 11
Tripp Lite SU6K, SUIOK manual LCD Display Select Switch, Operation on BYPASS-VOLTAGE OUT of Range, Operation on Overload