DRY CONTACT INTERFACE:

This female DB9 contact-closure port allows your UPS to send contact-closure signals to indicate that it is on battery back up mode and if its batteries are running low. The port can also receive a remote shutdown signal.

Pin assipnment;

lmin.U.3mA

L O W B A T T E R Y

I - REMOTE SHUTDOWN SIGNAL

 

FROM EXTERNAL

b

COY NC

I f

I

C

1

I

I SIGNALFROM

I

COMPUTER

.' !

 

MAXIMUM CAPACITY OF DRY CONTACT:

AC250Vn4

DC30vnA

DRY CONTACT INTERFACE TABLE

 

UPS Operating

Pin 8,3

Pin 1,3

Mode

 

 

Normal

OPEN

OPEN

Back Up

CLOSE

 

Low Battery

CLOSE

CLOSE

*Inactive: may be in either state.

REMOTE EMERGENCY POWER OFF:

This R J 11 modular jack allows remote emergency shutdown.

Pin assignment lSU6K Shown]

Pin 1

If there is a short between pins 2 and 3, 2 and 5, 4 and 5, or 3 and 4, the UPS will power off.