UPS LOCATION

Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not stack the UPS Systems or external battery packs.

INPUTAND OUTPUT CONNECTION

WIRING SELECTION

Choose appropriate cabling (depending on current carried; see chart below) to connect your UPS to an AC power supply and your equipment to your UPS:

MODEL

RATED INPUT

RATED OUTPW

RATED OUE'UT

OUTPUT

 

CURRENT

CURRENT

CURRENT

PROTECnON

 

208/240 I0 3 Wlre

120-208/240V 1 0 3 Wlre

120V 103Wlre

CIRCurr

SU6K

30A 8 AWG (8mm1/60"C)

30A 8 AWG (8mm1/6W)

2 x 32A 6 AWG [14rnm1/60"C)

32A

SU IOK

50A6AWG (14mrn1/60"C)

50A6AWG (14mm2/60"C)

2 x 50A4 AWG (22mmv/6(PC)

63A

WIRING CONNECTIONS

Connect your wiring to the input and output terminal blocks located on the lower rear panel of your UPS (seefigure below). Before cable connection, turn the UPS OFF and pull out the fuse holder. Ensure the cable is fitted with a cable sleeve and is secured by a connector clamp. The minimum tightening torque is 35 Ibs. per square inch. Connect the ground wire (typically colored green and yellow) to the terminal marked with the letter "G."

Cable Connection for 6kVA or lOkVA Output (6kVAshown)

AC INPUT

L U O V

156-264V50/60HZ

CAUTION: Observe the appropriate

 

cable connection regulations 1e.g.

 

National Electrical Code (NEC) in

TOTH,"AEkDING

the U.S.] at all times. Using cables

of improper size may damage your

(GROUND)

equipment and cause fire hazards.

+

Ground the UPS and the load

 

equipment a s shown in the figure.

 

GROUND UPS CONNECTION

LOAD 1

LOAD 2

LOAD 3

Page 7
Image 7
Tripp Lite SU6K, SUIOK manual UPS Location, Inputand Output Connection, Cable Connection for 6kVA or lOkVA Output 6kVAshown