Tripp Lite SU6K, SUIOK manual BA77ERY CONDITION VERIFICATION, Initial Bavery Charging Optional

Models: SU6K SUIOK

1 17
Download 17 pages 33.77 Kb
Page 9
Image 9
BA77ERY CONDITION VERIFICATION

BA77ERY CONDITION VERIFICATION

When the UPS is operating from battery power, the alarm and LCD Display will both alert you to the UPS battery's charge condition.

Batterv Charge Condition

Alarm

E D Dis~lav

 

FULL

Short Beep (every 2 seconds)

ON BAlTERY

 

 

 

BA'IT = XXV W

o

LOW

Short Beep (every 1/2 second)

BA'ITERY LOW

 

 

 

B A T = XXV W

o

UNDER

Continuous Beep

BA'ITERY UNDER

 

 

SHUT DOWN

 

INITIAL BAVERY CHARGING (OPTIONAL)

Your UPS System's battery is fully charged prior to shipping. However, if your UPS has been stored for an extended period, recharge its battery for 8 hours. To charge, turn on the AC Input Breaker. The LCD Display will illuminate and indicate "ON BYPASS." DO NOT turn on the AC Output Breaker to apply the load until the battery is fully charged. Once the UPS is in use, it will charge the batteries and maintain the charge level automatically.

TURNING THE UPS ON

Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Key is set to NORMAL.

Turn the AC Input Circuit Breaker ON, then turn the Output Circuit Breakers ON.

If your AC input is providing power normally within your selected range (see Input Voltage Selection, pg. 6, and Specs, pg. 17). your connected load will energize. However, the UPS'S inverter is not yet on. Press the front "ON/OFF" switch ON to begin inverter operation.

If your AC input is not providing power normally, you have the option of starting from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the "ON/OFF" switch for three seconds to start your UPS in "ON BA'ITERY mode. Note that some electronic equipment may draw more amps during startup: when starting from battery, consider reducing the initial load on the UPS.

The UPS will perform a brief self-test and show the results on the LCD Display. (See Self-Test section, pg. 10, for display sequence.)After a successful self-test, the UPS will provide AC power from the inverter to your load.

TURNING THE UPS OFF

Press the front "ON/OFFmSwitch OFF. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display will show "ON BYPASS."

Turn the AC Input and Output Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.

Page 9
Image 9
Tripp Lite SU6K BA77ERY CONDITION VERIFICATION, Initial Bavery Charging Optional, Turning The Ups On, Turning The Ups Off