BATERY CHARGE WARNlNGS

Since your UPS can provide battery backup only for as long a s the batteries remain charged, these warnings should be acted on immediately.

Battery Charge Warning

LCD Display Message

Battery charge nearly depleted

BATTERYLOW

AC/DC charger not operating

CHARGERFAILURE!

OPERATIONUNDERSHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the "Input," "Output" and "Bypass" LEDs will be illuminated.

Condition

LCD Display Message

Extended Overload (>1500%)

OVERLOAD 150%

 

SHUTDOWN

Output Short Circuit

SHORTClRCUlTl

 

SHUTDOWN

Remote Shutdown Command

REMOTE

(FROM DB9 INTERFACE)

SHUTDOWN

Remote Shutdown Command

EMERGENCYSTOP!

(from RJ 11 interface)

SHUTDOWN

Internal Faults

INVERTERTOOLO

 

SHUTDOWN

 

INVERTERTOOHI

 

SHUTDOWN

 

DC BUS +/- HIGH/LOW

 

SHUTDOWN

 

OVERTEMPERA'IURE

 

SHUTDOWN

OPERATION OF MANUAL BYPASS SWITCH

Turn this switch to "BY- PASS" before performing any maintenance on the

UPS with the connected A C ~ N ~ U ~ load supported. Connected equipment will receive

filtered AC mains power, but will not receive battery power in the event of a blackout.

-

UAHUAL BYPASS SWITCH

l ~ ~ U TFROUE ~ W E *C L I N ~

SWITCHING UPS TO "BYPASS" MODE

Turn the "ON/OFFn Switch OFF. (LCD will read "ON BYPASS.")

Turn the "Manual Bypass" Switch clockwise from NORMAL to BYPASS. Turn the AC Input Circuit Breaker OFF.

Open battery fuse holders and remove the battery fuses from all battery packs and from all SUGK models.

SWITCHING UPS TO "NORMAL"MODE

Replace all battery fuses in the battery fuse holders and close the battery fuse holders.

Turn the AC Input Circuit Breaker ON.

Turn the "Manual Bypass" Switch counterclockwise from BYPASS back to NORMAL.

Turn the "ON/OFF Switch ON.

Page 12
Image 12
Tripp Lite SUIOK, SU6K manual Batery Charge WARNlNGS, Operationundershutdown, Operation of Manual Bypass Switch