RS-232 INTERFACE

This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses RS-232 communications to report UPS status and power conditions. Using this port, M p p Lite software can monitor and manage network power and automatically save open files and shut down equipment during a blackout. Contact M p p Lite Customer Support at (773)869-1233 for informa- tion on available SNMP, network management and connectivity software and products.

RS-232 signals and operations include: load level, battery status, battery level. operation mode, AC input voltage, AC output voltage, AC input frequency. temperature inside unit, set shut-down delay time, enable/disable alarm and remote shutdown.

Hardware:

Baud Rate:

2400 BPS

Pin assienment;

Data Length:

8 bits

Pin 2:

TXD (Transmit Data)

Stop Bit:

1 bit

Pin 3:

RXD (ReceivingData)

Parity:

NONE

Pin 5:

GND (Signal Ground)

AS-400 INTERFACE:

This female DB9 port connects your UPS to an IBM AS-400 computer via the included AS-400 cable.The port uses AS-400 communications to report UPS status. It can be used to allow an AS-400 to automatically save open files and shut down its operating system during a blackout. AS-400 protocol includes: operation on inverter, operation on AC power supply, operation on battery and low battery alarm.

pin assimment:

Pin 5:

Common

Pin 6:

Operation on AC power supply

Pin 7:

Low battery alarm

Pin 8:

Operation on inverter

Pin 9:

Operation on battery

LOW BATTERY

INVERTER

E l

I

1941 I

AS-400INTERFACE TABLE

 

 

 

 

Pin 6,5

Pin 7.5

Pin 8.5

Pin 9,5

Battery

OFF

 

ON

ON

Low Battery

OFF

ON

ON

ON

Direct Mains Supply

ON

OFF

OFF

OFF

Inverter

OFF

*

ON

*

*Inactive:may be in either state.