Vanguard Heating PM200, PM400 operation manual Side Wall Venting Installation, see illustration #2

Models: PM200 PM400

1 28
Download 28 pages 37.67 Kb
Page 24
Image 24
SIDE WALL VENTING INSTALLATION

Appendix A

SIDE WALL VENTING INSTALLATION

SIDE WALL VENTING INSTALLATION

(see illustration #2)

1.Install wall thimble into wall, observing the aforementioned rules and/or local building codes. Select the point of wall penetration where the minimum 114” per foot of slope (6.4 mm per 305 mm) can be maintained. The pipe can be located between joists spaced 16” (400 mm) on centre. The pipe may be mortared in directly without using a wall thimble, if the wall is non-combustible. Penetrating a combustible wall requires the use of a wall thimble. A framed opening is required to insert the thimble halves. The thimble is adjustable for different wall thicknesses. Caulk around outside edge of plates as necessary and fasten to wall using suitable screws or nails. The vent pipe must be sealed at wall thimble as per code regarding continuous vapor barrier.

2.The system can now be assembled through the thimble (attach the termination first - note “UP” arrow) and then back to the appliance as per illustration using JOINT PROCEDURE as described on page #3. A gear clamp (or locking band) must be installed around the pipe in position so that the system cannot be removed in or out of wall. This applies to both combustible and non-combustible walls.

22

Page 24
Image 24
Vanguard Heating PM200, PM400 operation manual Side Wall Venting Installation, see illustration #2