APPENDIX A
TYPICAL SPECIAL STAINLESS STEEL VENTING
For use with Category II, III, IV appliances
Contact Local Building or Fire Officials About Restrictions and Installation Inspections in your area as well as National codes:
USA
CANADA
Please refer to appliance manufacturers’ instructions to determine proper sizing and connection of venting system to appliance, including maximum horizontal length, maximum height, and installation clearances (air spaces). The proper operation of the vent system and appliance requires parts specified by
PARTS LIST
COMPONENT | 3” SYSTEM CAT. # | 4” SYSTEM CAT. # | COMPONENT | 3” SYSTEM CAT. # | 4” SYSTEM CA1~# |
|
|
|
|
|
|
10 FOOT PIPE | SVEPWC0310 | SVEPWC04I0 | ADJUST. FLASHING | SVSADJ03 | SYSADJ04 |
|
|
|
|
|
|
8 FOOT PIPE | SVEPWC0308 | SVEPWC0408 | REDUCER 4” TO 3” | SVSERWC0403 | SVSR0404 |
|
|
|
|
|
|
5 FOOT PIPE | SVEPWC0305 | SVEPWC0405 | FLAT FLASHING | SVSSCS03 | SVSSCS04 |
4 FOOT PIPE | SVEPWC0304 | SVEPWC0404 | LOCKING BAND | SVSLBX03 | SVSLBX04 |
|
|
|
|
|
|
3 FOOT PIPE | SVEPWC0303 | SVEPWC0403 | FIRESTOP SUPPORT | SVSFSS03 | SVSFSS04 |
|
|
|
|
|
|
2 FOOT PIPE | SVEPWC0302 | SVEPWC0402 | FTRESTOP SPACER | SVSFSX03 | SVSFSX04 |
|
|
|
|
|
|
1 FOOT PIPE | SVEPWC0301 | SVEPWC0401 | TERMINATION TEE | SVSTTX03 | SVSTTX04 |
|
|
|
|
|
|
6 INCH PIPE | SVEPWC03.5 | SVEPWCO4.5 | TERMINATION BOX | SVSRTX03 | SVSRTX04 |
|
|
|
|
|
|
90 0ELBOW | SVEEWC0390 | SVEEWC0490 | RAIN CAP | SVSRCX03 | SVSRCX04 |
45 ELBOW | SVEEWC0345 | SVEEWC0345 | TOP SUPPORT | SVSLSX03 | SVSLSX04 |
|
|
|
|
|
|
HORJZ. DRAIN TEE | SVEDWC03 | SVEDWC04 | STORM COLLAR | SVSSCX03 | SVSSCX04 |
|
|
|
|
|
|
VERTICAL DRAIN TEE | SVEVWC03 | SVEVWC04 | GE106X |
| |
WALL THIMBLE | SVSWTX03 | SVSWTX04 | WM TERM COUPLING | SVSTPX03 |
|
|
|
|
|
|
|
WM GV STARTER | SVEWMG03 |
| AMETEK FAN CONN. | SVSACA03 |
|
|
|
|
|
|
|
DRAIN TUBE KIT | SVEDTK |
| WM CGI STARTER | SVEWMFA03 |
|
When the
1.A venting system that exits the structure through a sidewall or the like, shall terminate not less than 12 inches (254 mm) above the ground (see illustration # 2, page 4).
2.The termination of a system shall be located above the snow line in geographical areas where snow accumulates. The termination area should be kept clear of snow and ice at all times.
3.The vent shall not terminate less than 7 ft. (2.13 m) above a paved sidewalk or driveway.
4.The termination shall be 6 ft. (1.8 m) or more from the combustion air intake of any appliance.
5.The system shall terminate more than 3 ft. (.91 m ) from any other building opening, gas utility meter, service regulator or the like.
6.Exterior mounted venting systems should be enclosed below the roof line with a chase to limit condensation and protect against mechanical failure.
NOTES:
A.The
B.Except for installation in one and two family dwellings, a venting system that extends through any zone above that on which the connected appliance is located shall be provided with an enclosure having a fire resistance rating equal to or greater than that of the floor or roof assemblies through which it passes
C.Do not place any type of insulation in any required air spaces surrounding the venting system.
D.A termination must be used on all installations to assure proper operation and to prevent debris from entering the venting system.