Vanguard Heating PM400, PM200 operation manual Examples of ACCEPTABLE VENT PIPING/ See Appendix A

Models: PM200 PM400

1 28
Download 28 pages 37.67 Kb
Page 7
Image 7
Examples of ACCEPTABLE VENT PIPING/ See Appendix A

any door, opening window or gravity air inlet into any building. It shall also have a minimum horizontal clearance of four feet from any electric meter, gas meter, regulator, relief valve or other equipment.

-The vent terminal shall be located not less than seven feet above grade when it is adjacent to public walkways.

-The bottom of the vent terminal shall be located at least twelve inches above grade or ground or the normally expected snow accumulation level.

The snow level may be higher on walls exposed to prevailing winds.

-Avoid areas where local experience indicates that condensate drippage may cause problems, such as above planters, patios, public walkways or areas where condensate or vapor could cause a nuisance or hazard, or where its discharge could be detrimental to the operation of regulators, relief valves or other equipment.

Examples of ACCEPTABLE VENT PIPING/ See Appendix A

MANUFACTURER

MODEL

MATERIAL

 

3”

4”

 

 

SPECIFICATION

Part Name

Part Number

Part Number

 

 

 

 

 

 

Heat-Fab Inc.

Saf-T-Vent

AL 29-4C

Tee

7390TEE

7490TEE

38 Haywood St.

 

Stainless Steel

Rain Cap

5300C1

5400C1

Greenfield, MA 01301

 

 

Mitre I Straight

7390GC

-

Z-Flex US, Inc.

Z-Vent

AL 29-4C

Tee

#02SVSTTX-3

#02SVSTTX-4

20 Commerce Park North

 

Stainless Steel

Rain Cap

#02VRSRCX03

#02VRSRCX04

Bedford, NH 03110

 

 

Termination Box

#02SVSRTX-3

#02SVSRTX-4

 

 

 

 

 

 

Flex-L International, Inc.

StaR-34

AL 29-4C

Termination Tee

SRTT03

SRTT04

6385 Kennedy Rd

 

Stainless Steel

Wall Thimble

SRWT153

SRWT154

Mississauga, ON

 

 

 

 

 

L5T2W4

 

 

 

 

 

GAS PIPING

The gas inlet pipe size is 3/4 inch NPT, male thread, located at the lower right front corner of the appliance. The gas supply piping must be sized to adequately provide the input BTU/hr rate for the appliance at the specified flowing pressure (see table 1). The maximum inlet gas pressure must not exceed the maximum value shown in table 1. The minimum gas pressure shown in Table 1 is for purposes of input adjustment.

FLOWING Gas Pressure Requirement (not static)

Inches W.C. (Water Column)

Natural Gas/LP

Incoming Line Pressure

Manifold

 

Minimum

Maximum

Pressure

PM200

4.5”NG/10”LP

10.5”NG/14”LP

3.5”NG/7.5”LP

PM400

4.5”NG/10”LP

10.5”NG/14”LP

3.5”NG/7.5”LP

 

TABLE 1

 