AIR FOR

WARNING ICONG 001WARNING

COMBUSTION

 

If the area in which the heater may be operated is smaller than

AND

that defined as an unconfined space, provide adequate combus-

tion and ventilation air by one of the methods described in the

VENTILATION

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or appli-

Continued

cable local codes.

VENTILATION AIR

 

 

Ventilation Air From Inside Building

 

This fresh air would come from an adjoining unconfined space. When ventilating to

 

an adjoining unconfined space, you must provide two permanent openings: one within

 

12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces

 

(see options 1 and 2, Figure 4). You can also remove door into adjoining room (see

 

option 3, Figure 4). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1,

 

Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills

 

or ducts.

 

 

 

WARNING ICONG 001WARNING

 

Rework worksheet, adding the space of the adjoining unconfined

 

space. The combined spaces must have enough fresh air to supply all

 

appliances in both spaces.

 

 

12"

 

Ventilation Grills

Ventilation

Into Adjoining Room,

Option 2

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Figure 4 - Ventilation Air from Inside Building Shown with Optional Mantel

8

103670

Page 8
Image 8