Alcove Installations

Alcove Installations

Because of their restricted air flow and heat retention characteristics, specific construction requirements and special clearances apply to installations into alcoves. No stove or chimney connector heat shields are used in alcove installations.

ALCOVE INSTALLATION OF THE MADISON IS NOT PERMITTED IN CANADA.

Construction Requirements

The following illustrations show noncombustible ceiling framing and maximum and minimum permitted dimen- sions for alcove construction.

 

 

7/16” Durock®

36"

Use recommended

(or equivalent)

Max.

floor protection

spaced 1” off

 

 

wood studs on

 

 

noncombustible

 

 

spacers

 

48" Min.

ST502

 

 

Fig. 19 Alcove floor plan. Sheetrock on front face butts to Du- rock® (or equivalent) alcove lining.

Vermont Castings Madison

 

 

 

ST504

Fig. 21

Cutaway perspective of alcove installation.

 

 

Existing Combustible

 

 

 

Framing

24"

 

 

 

 

 

 

 

11"

Metal studs

 

Min.

 

 

support 7/16”

 

 

Durock® (or

 

36"

equivalent)

 

 

Min.

ceiling

 

 

 

 

 

 

 

14���"

 

Joist Shield (Supplied by Chimney Manufacturer)

 

 

48" Min.

 

ST505

 

 

 

 

 

 

 

 

 

Fig. 22 Reflected ceiling plan.

 

 

1” air gap top and bottom, on both sides and back wall

Metal

StudConstruction Requirements

Combustible facing may overlap metal studs by only 1”

7/16” Durock® (or equivalent)

Ceiling sup- port package extends 2” below Durock® (or equivalent) ceiling

1” air gap, top, bottom, on both sides and back wall

62" Min.

65" to Alcove Ceiling

ST503

NOTE: From 62” to 65” must be covered by a noncom- bustible material.

ST506

Fig. 20 Alcove side section.

Fig. 23 Front view: 65” minimum clearance from hearth to combustibles on front face. Combustible facing may overlap metal studs by only 1”. It should not extend below the height of the noncombustible ceiling.

30001453

11

Page 11
Image 11