Vermont Castings Madison
• Placing a chimney connector pipe inside a section of |
9” (230 mm) diameter, |
Min. 18”
(460mm) Chimney clearance to sheet steel 2” (51mm)
supports and combustibles Min.
chimney, with two inches of air space between the |
chimney section and combustibles. (Fig. 10) |
Canadian Requirements:
In Canada, the Canadian Standards Association has established specific guidelines regarding wall pass- though design. Figure 11 shows one approved method in which all combustible material in the wall is cut away
Chimney Flue
Min. 18” (460mm)
Chimney Connector
24 ga.Sheet Steel Support
to provide the required 18” (457mm) clearance around the connector. The resulting space must remain empty. A
In Canada, this type of installation must conform to
24 ga. Sheet | Masonry Chimney con- |
Steel Support | |
(one side only) | structed to |
ST276
Fig. 11 CSA approved Wall Pass-through.
Floor Protection
Atremendous amount of heat radiates from the bottom plate of your Madison. The floor area directly under and around the stove will require protection from radiant heat as well as from stray sparks or embers that may escape the firebox.
Heat protection is provided through the use of a Ver- mont Castings Bottom Heat Shield #1892. Spark and ember protection must be provided by a floor protector constructed with noncombustible material as specified.
Chimney clearance to sheet steel supports and combustibles
Steel Thimble with two 1” (25mm) Ventilated Channels
Masonry Chimney construct- | Chimney Flue |
| |
ed to NFPA 211 |
|
ST274
2” (51mm) Min.
Min. 6” (152mm)
Chimney Connector
Glass Fiber
Insulation
24 ga.Sheet
Steel Supports
Most installations will require that the bottom heat shield be attached. Only when the stove is placed on a complete- ly noncombustible surface such as unpainted concrete over earth may it be used without the heat shield.
Even when the bottom heat shield is installed, you must provide special protection to the floor beneath. For installations with the heat shield attached, use a non- combustible floor protector such as 1/4”
Fig. 9 Wall Pass-through using single wall chimney connector with a ventilated steel thimble.
Chimney clearance to sheet steel | 2” (51mm) |
supports and combustibles | Min. |
Protection requirements vary somewhat between the United States and Canada as follows:
For U.S. installations the floor protector is required under the stove and must extend at least 18” from the
ST275
2” (51mm) Min. air space
Prefab Chim-
ney
Section
24 ga. Sheet Steel Supports
Flue | 2” (51mm) Min. |
Chimney | Chimney Con- |
| nector |
| Prefab |
| Chimney |
| Section |
| 24 ga. Sheet |
| Steel Supports |
| Masonry Chimney construct- |
| ed to NFPA 211 |
front of the stove (“D”, Fig. 12), at least 4” from the right side and rear (“C”, Fig. 12) and 16” from the left side (“E”, Fig. 12). It must also extend under the chimney connector and 2” to either side (“F”, Fig. 12).
To meet these requirements, a floor protector must be at least 48” wide (“A”,Fig. 12) and 48” deep (“B”,Fig. 12)
In Canada, a noncombustible floor protector is required under the heater also. The floor protector must extend 18” (457mm) to the front (D), and 8” (203mm) from the
Fig. 10 Wall Pass-through with ventilated steel thimble.
right side (C) and rear (C) and 18” (457mm) from left side (E).
8 | 30001453 |